Output - Pepperl+Fuchs PS1000-A6-48.5 Technical Information

Table of Contents

Advertisement

Power Supply PS1000-A6-48.5

Output

8
Output
Output voltage
Adjustment range
Factory settings
Line regulation
Load regulation
Ripple and noise voltage
Output current
Overload behavior
Short-circuit current
Output capacitance
1
Power boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
2
Hiccup mode
At heavy overloads (when output voltage falls below 26V), the power supply delivers continuous output current for 2s.
After this, the output is switched off for approx. 18s before a new start attempt is automatically performed.
This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally.
See Figure 8.3
3
Discharge current of output capacitors is not included.
Nom.
48V
Min.
48-56V
Max.
58.0V
Typ.
48.0V
Max.
10mV
Max.
50mV
Max.
50mVpp
1
Nom.
6.0A
Nom.
5.4A
Nom.
4.0A
1
Nom.
5.2A
Nom.
4.6A
Nom.
3.4A
Typ.
15A
Continuous current Output voltage above 26Vdc, see Figure 8.1
2
Hiccup mode
3
Min.
6.3A
3
Max.
7.7A
Max.
2.2A
Min.
14.5A
Typ.
16.0A
Typ.
960µF
Guaranteed value
This is the maximum output voltage which can occur
at the clockwise end position of the potentiometer
due to tolerances. It is not a guaranteed value which
can be achieved.
±0.2%, at full load and cold unit
Between 85 and 300Vac
Between 0 and 12A, static value, see Figure 8.1
Bandwidth 20Hz to 20MHz, 50Ohm
At 48V and an ambient temperature below 45°C,
see Figure 18.1
At 48V and 60°C ambient temperature,
see Figure 8.1
At 48V and 70°C ambient temperature,
see Figure 18.1
At 56V and an ambient temperature below 45°C,
see Figure 18.1
At 56V and 60°C ambient temperature,
see Figure 8.1
At 56V and 70°C ambient temperature,
see Figure 18.1
For minimal 12ms once every five seconds,
see Figure 8.2.
The output voltage stays above 40V.
See chapter 26.1 for more peak current
measurements. For AC 100V mains, the pulse length
is shorter than 12ms.
Output voltage below 26Vdc, see Figure 8.1
Load impedance <90mOhm, see Figure 8.3
Load impedance <90mOhm, see Figure 8.3
Average (R.M.S.) current, load impedance 50mOhm,
see Figure 8.3
Up to 12ms, load impedance <90mOhm,
see Figure 8.2
Up to 12ms, load impedance <90mOhm,
see Figure 8.2
Included inside the power supply
13

Advertisement

Table of Contents
loading