Table of Contents
loading

Summary of Contents for Pepperl+Fuchs HiD2022 Series

  • Page 1 PROCESS AUTOMATION MANUAL Functional Safety SMART Transmitter Power Supply HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* ISO9001...
  • Page 2 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship"...
  • Page 3: Table Of Contents

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Content 1 Introduction........4 1.1 Contents .
  • Page 4: Introduction

    Additionally, the following parts may belong to the documentation, if applicable: • EU-type of examination • EU declaration of conformity • Attestation of conformity • Certificates • Control drawings • FMEDA report • Assessment report • Additional documents For more information about functional safety products from Pepperl+Fuchs see www.pepperl-fuchs.com/sil.
  • Page 5: Safety Information

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Introduction Safety Information Target Group, Personnel Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator. Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product.
  • Page 6: Symbols Used

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Introduction Symbols Used This document contains symbols for the identification of warning messages and of informative messages. Warning Messages You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid property damage.
  • Page 7: Product Description

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Product Description Product Description Function HiD2022 This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire and 3-wire SMART transmitters, and can also be used with 2-wire SMART current sources. It transfers the analog input signal to the safe area as an isolated current value. Digital signals may be superimposed on the input signal in the hazardous or non- hazardous area and are transferred bi-directionally.
  • Page 8 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Product Description KFD2-STC5-1, KFD2-STC5-2 This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device supplies 2-wire and 3-wire SMART transmitters, and can also be used with 2-wire SMART current sources. It transfers the analog input signal as an isolated current value.
  • Page 9 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Product Description KFD2-STC5-Ex1(.H), KFD2-STC5-Ex2 This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire and 3-wire SMART transmitters, and can also be used with 2-wire SMART current sources. It transfers the analog input signal to the safe area as an isolated current value. Digital signals may be superimposed on the input signal in the hazardous or non- hazardous area and are transferred bi-directionally.
  • Page 10 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Product Description KFD2-STV5-1-1, KFD2-STV5-2-1 This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device supplies 2-wire and 3-wire SMART transmitters, and can also be used with 2-wire SMART current sources. It transfers the analog input signal as an isolated current value.
  • Page 11 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Product Description KFD2-STV5-Ex1.2O-1, KFD2-STV5-Ex1.2O-2 This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire and 3-wire SMART transmitters, and can also be used with 2-wire SMART current sources. It transfers the analog input signal to the safe area as two isolated output signals. Digital signals may be superimposed on the input signal in the hazardous or non- hazardous area and are transferred bi-directionally.
  • Page 12: Marking

    • Non-safety relevant interfaces: none The HART communication is not relevant for functional safety. Note! For corresponding connections see datasheet. Marking Pepperl+Fuchs GmbH Lilienthalstraße 200, 68307 Mannheim, Germany Internet: www.pepperl-fuchs.com HiD2022, HiD2022SK, Up to SIL 2 KFD2-STC5-1, KFD2-STC5-2, KFD2-STC5-Ex1, KFD2-STC5-Ex1.H,...
  • Page 13: Planning

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Planning Planning System Structure 3.1.1 Low Demand Mode of Operation If there are two control loops, one for the standard operation and another one for the functional safety, then usually the demand rate for the safety loop is assumed to be less than once per year.
  • Page 14: Assumptions

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Planning Assumptions The following assumptions have been made during the FMEDA: • Failure rate based on the Siemens standard SN29500. • Failure rates are constant, wear is not considered. • External power supply failure rates are not included. •...
  • Page 15: Safety Function And Safe State

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Planning SIL 3 Application SIL 3 can be reached if the two outputs of the device are connected to the same control interface and evaluated if the deviation remains below 2 %. • The device shall claim less than 10 % of the total failure rate for a SIL 3 safety loop.
  • Page 16 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Planning Functional Safety Connection Configuration for KFD2-***-(Ex)1.2O* Devices KFD2-***-(Ex)1.2O* SIL 2 transmitter DCS 1/ ESD system 1 Output 1 Input A DCS 2/ ESD system 2 Output 2 Input B Figure 3.1 SIL 2 application KFD2-***-(Ex)1.2O* SIL 3 transmitter ESD system...
  • Page 17: Characteristic Safety Values

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Planning Characteristic Safety Values KFD2-STC5-1, KFD2-STC5-Ex1, KFD2-STC5-Ex1.H, KFD2-STV5-1-1, KFD2-STV5-Ex1-1, KFD2-STV5-Ex1-2 HiD2022, HiD2022SK, KFD2-STC5-2, KFD2-STC5-Ex2, KFD2-STV5-2-1, KFD2-STV5-Ex2-1, KFD2-STV5-Ex2-2 Parameters acc. to IEC 61508 Characteristic values Assessment type and documentation FMEDA report Device type Operating mode Low Demand Mode or High Demand Mode Safety function Transfer of analog signals SIL (SC)
  • Page 18 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Planning KFD2-STC5-1.2O, KFD2-STC5-Ex1.2O, KFD2-STC5-Ex1.2O.H, KFD2-STV5-Ex1.2O-1, KFD2-STV5-Ex1.2O-2 Parameters acc. to IEC 61508 Characteristic values Assessment type and FMEDA report documentation Device type Operating mode Low Demand Mode or High Demand Mode Safety function Transfer of analog signals SIL (SC) Input and output function 1 output used in safety function...
  • Page 19: Useful Life Time

    As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer and plant operator can extend the useful lifetime. Our experience has shown that the useful lifetime of a Pepperl+Fuchs product can be higher if the ambient conditions support a long life time, for example if the ambient temperature is significantly below 60 °C.
  • Page 20: Mounting And Installation

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Mounting and Installation Mounting and Installation Installing the device 1. Observe the safety instructions in the instruction manual. 2. Observe the information in the manual. 3. Observe the requirements for the safety loop. 4. Connect the device only to devices that are suitable for this safety application. 5.
  • Page 21: Operation

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Operation Operation Danger! Danger to life from missing safety function If the safety loop is put out of service, the safety function is no longer guaranteed. • Do not deactivate the device. • Do not bypass the safety function. •...
  • Page 22 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Operation Proof Test Procedure 1. Put out of service the entire safety loop. Protect the application by means of other measures. 2. Prepare a test set-up, see figures below. 3. Test the devices. Verify the current values as given in table below. 4.
  • Page 23 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Operation Signal calibration KFD2-STV5-Ex2-2 4 mA ... 20 mA Multimeter (mA) 500 Ω 250 Ω Multimeter (mA) 500 Ω 250 Ω supply 24 V DC Power Zone 0, 1, 2 Zone 2 supply Div. 1, 2 Div.
  • Page 24 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Operation Proof Test for Devices with Splitter Function (1.2O) Step No. Input value (mA) Output value Current source/current Voltage source (V) for Voltage source (V) for sink (mA) for KFD2- KFD2-STV5-Ex1.2O-1 KFD2-STV5-Ex1.2O-2 STC5-(Ex)1.2O(.H) 20.0 20.0 ± 0.4 5.0 ±...
  • Page 25 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Operation Signal calibration KFD2-STV5-Ex1.2O-2 4 mA ... 20 mA Multimeter (mA) 500 Ω 250 Ω Multimeter (mA) 500 Ω 250 Ω supply 24 V DC Power Zone 0, 1, 2 Zone 2 supply Div. 1, 2 Div.
  • Page 26 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Operation Proof Test for 2-Channel H-System Devices Step No. Input value (mA) Output value Current source/current sink (mA) for HiD2022(SK) 20.0 20.0 ± 0.4 12.0 12.0 ± 0.4 4.0 ± 0.4 23.0 23.0 ± 0.4 <...
  • Page 27: Maintenance And Repair

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Maintenance and Repair Maintenance and Repair Danger! Danger to life from missing safety function If the safety loop is put out of service, the safety function is no longer guaranteed. • Do not deactivate the device. •...
  • Page 28: List Of Abbreviations

    Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* List of Abbreviations List of Abbreviations Emergency Shutdown Failure In Time in 10 FMEDA Failure Mode, Effects, and Diagnostics Analysis Probability of safe failure  Probability of dangerous detected failure  Probability of dangerous undetected failure ...
  • Page 29 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Notes...
  • Page 30 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Notes...
  • Page 31 Functional Safety HiD2022*, KFD2-STC5-(Ex)*, KFD2-STV5-(Ex)* Notes...
  • Page 32 PROCESS AUTOMATION – PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl+Fuchs GmbH 68307 Mannheim · Germany Tel. +49 621 776-0 E-mail: info@de.pepperl-fuchs.com For the Pepperl+Fuchs representative closest to you check www.pepperl-fuchs.com/contact www.pepperl-fuchs.com Subject to modifications Copyright PEPPERL+FUCHS • Printed in Germany DOCT-5695 09/2017...