Terminals And Wiring - Pepperl+Fuchs PS1000-A6-48.5 Technical Information

Table of Contents

Advertisement

Power Supply PS1000-A6-48.5

Terminals and Wiring

15
Terminals and Wiring
The terminals are IP20 finger safe constructed and suitable for field- and factory wiring.
Type
Solid wire
Stranded wire
American Wire Gauge
Wire diameter (including ferrules)
Wire stripping length
Screwdriver
Recommended tightening torque
Connecting Terminals
1.
Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum
90°C for ambient up to 70°C minimum.
2.
Follow national installation codes and installation regulations!
3.
Ensure that all strands of a stranded wire enter the terminal connection!
4.
Unused terminal compartments should be securely tightened.
5.
Ferrules are allowed.
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long
as the average output current through one terminal pin does not exceed 25A. If the current
is higher, use a separate distribution terminal block as shown in Figure 15.2.
Figure 15.1
22
Input and output
Screw termination
2
Max. 6mm
2
Max. 4mm
AWG 20-10
Max 2.8mm
7mm / 0.28inch
3.5mm slotted or cross-head No 2
Max. 1Nm, 9lb-in
P ower
S upply
- -
+ +
Output
Maximal 15A continuous for C P 5.241-S 2
Maximal 25A continuous for all other units
Daisy chaining of outputs
DC-OK-Signal
Push-in termination
Max. 1.5mm
Max. 1.5mm
AWG 24-16
Max. 1.6mm
7mm / 0.28inch
Not required
Not available
P ower
S upply
Load
- -
+ +
Output
-
+
max. 25 A
continuous
2
2