Ac Input - Pepperl+Fuchs PS1000-A6-12.16 Technical Information

Table of Contents

Advertisement

Power Supply PS1000-A6-12.16

AC Input

5
AC Input
AC input
AC input range
Allowed voltage L or N to earth Max.
Input frequency
Turn-on voltage
Shut-down voltage
External input protection
Input current
Typ.
1
Power factor
Typ.
2
Crest factor
Typ.
Start-up delay
Typ.
Rise time
Typ.
Typ.
Turn-on overshoot
Max.
1
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
2
The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Figure 5.1
Figure 5.2
Nom.
AC 100-240V
Min.
85-264Vac
Min.
264-300Vac
300Vac
Nom.
50–60Hz
Typ.
80Vac
Typ.
70Vac
Typ.
55Vac
See recommendations in chapter 27.3
AC 100V
AC 120V
2.11A
1.74A
0.99
0.99
1.5
1.65
300ms
290ms
18ms
18ms
35ms
35ms
200mV
200mV
P
OUT
Input voltage range
Input
Voltage
Output
Voltage
S tart-up
delay
Turn-on behavior, definitions
Suitable for TN-, TT- and IT mains networks
Continuous operation
For maximal 500ms
Continuous, IEC 62103
±6%
Steady-state value, see Figure 5.1
Steady-state value, see Figure 5.1
Dynamic value (250ms)
AC 230V
0.92A
At 12V, 16A, see Figure 5.3
0.96
At 12V, 16A, see Figure 5.4
1.65
At 12V, 16A
240ms
See Figure 5.2
18ms
At 12V, 16A const. current load, 0mF
load capacitance, see Figure 5.2
35ms
At 12V, 16A const. current load, 16mF
load capacitance, see Figure 5.2
200mV
See Figure 5.2
R ated
input range
max.
500ms
85V
264V
300Vac
- 5%
R is e
Time
V
IN
9

Advertisement

Table of Contents
loading

Table of Contents