Technical Information
ISO9001

Advertisement

Table of Contents
loading

Summary of Contents for Pepperl+Fuchs PS1000-A6-24.5

  • Page 1 PS1000-A6-24.5 Power Supply Technical Information ISO9001...
  • Page 2 Phone: +49 621 776 - 0 E-mail: info@de.pepperl-fuchs.com North American Headquarters Pepperl+Fuchs Inc. 1600 Enterprise Parkway Twinsburg, Ohio 44087 Phone: +1 330 425-3555 E-mail: sales@us.pepperl-fuchs.com Asia Headquarters Pepperl+Fuchs Pte. Ltd. P+F Building 18 Ayer Rajah Crescent Singapore 139942 Phone: +65 6779-9091 E-mail: sales@sg.pepperl-fuchs.com https://www.pepperl-fuchs.com...
  • Page 3: Table Of Contents

    Power Supply PS1000-A6-24.5 Contents Introduction ............5 Terminology and Abbreviations.
  • Page 4 Power Supply PS1000-A6-24.5 Contents...
  • Page 5: Introduction

    Power Supply PS1000-A6-24.5 Introduction Introduction The information given in this document is correct to the best of our knowledge and experience at the time of publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is subject to revision.
  • Page 6: Terminology And Abbreviations

    Power Supply PS1000-A6-24.5 Terminology and Abbreviations Terminology and Abbreviations PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol Earth, Ground This document uses the term earth which is the same as the U.S. term ground.
  • Page 7: Intended Use

    Power Supply PS1000-A6-24.5 Intended Use Intended Use This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control, monitoring and measurement equipment or the like. Do not use this device in equipment where malfunction may cause severe personal injury or threaten human life.
  • Page 8: Installation Instructions

    Power Supply PS1000-A6-24.5 Installation Instructions Installation Instructions Warning! Explosion hazard from live wiring of non-intrinsically safe circuits • Turn power off before working on the device. Protect against inadvertent re-powering. • Do not modify or repair the unit. • Do not open the unit as high voltages are present inside.
  • Page 9 Power Supply PS1000-A6-24.5 Installation Instructions Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, the 5mm can be reduced to zero.
  • Page 10: Ac Input

    Power Supply PS1000-A6-24.5 AC Input AC Input The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage. For suitable DC supply voltages see chapter 4 AC input Nom. AC 100-240V AC input range Min.
  • Page 11 Power Supply PS1000-A6-24.5 AC Input Input C urrent, typ. 1.5A 1.25 a) 100Vac b) 120Vac c) 230Vac 0.75 0.25 Output C urrent 0.5 1 Figure 5.3 Input current vs. output current at 24V output voltage P ower Factor, typ. 0.95 0.85...
  • Page 12: Dc Input

    Power Supply PS1000-A6-24.5 DC Input DC Input The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit.
  • Page 13: Input Inrush Current

    Power Supply PS1000-A6-24.5 Input Inrush Current Input Inrush Current An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
  • Page 14: Output

    Power Supply PS1000-A6-24.5 Output Output The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage. The output is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or "UltraCaps") with a capacitance >...
  • Page 15 Power Supply PS1000-A6-24.5 Output Output Voltage Adjus tment R ange A: continuous current B : intermittent current Output C urrent Figure 8.1 Output voltage vs. output current, typ. Output Voltage (dynamic behavior, < 12ms ) Adjus tment R ange Output C urrent 12.5...
  • Page 16: Hold-Up Time

    Power Supply PS1000-A6-24.5 Hold-Up Time Hold-Up Time The hold-up time is the time during which a power supply’s output voltage remains within specification following the loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is also on during this time.
  • Page 17: Dc-Ok Relay Contact

    Power Supply PS1000-A6-24.5 DC-OK Relay Contact DC-OK Relay Contact This feature monitors the output voltage on the output terminals of a running power supply. Contact closes As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
  • Page 18: Efficiency And Power Losses

    Power Supply PS1000-A6-24.5 Efficiency and Power Losses Efficiency and Power Losses AC 100V AC 120V AC 230V Efficiency Typ. 92.9% 93.6% 94.3% At 24V, 5A Typ. 92.7% 93.5% 94.5% At 24V, 6A (Power Boost) Average efficiency Typ. 91.3% 91.7% 92.0% 25% at 1.25A, 25% at 2.5A,...
  • Page 19 Power Supply PS1000-A6-24.5 Efficiency and Power Losses E fficiency Input Voltage 230 264Vac Figure 11.3 Efficiency vs. input voltage at 24V, 5A, typ. P ower L osses Input Voltage 230 264Vac Figure 11.4 Losses vs. input voltage at 24V, 5A, typ.
  • Page 20: Functional Diagram

    Power Supply PS1000-A6-24.5 Functional Diagram Functional Diagram Input F us e Input F ilter Output P ower P F C F ilter C onverter Input R ectifier C onverter Inrus h C urrent Limiter Output Voltage R egulator DC -ok...
  • Page 21: Front Side And User Elements

    Power Supply PS1000-A6-24.5 Front Side and User Elements Front Side and User Elements Output Terminals Two identical +poles and two identical -poles Positive output – Negative (return) output Output Voltage Potentiometer OUTPUT DC 24V 5A 24 - 28V DC-OK LED (green) On, when the output voltage is >90% of...
  • Page 22: Connection Terminals

    Power Supply PS1000-A6-24.5 Connection Terminals Connection Terminals The terminals are IP20 finger safe constructed and suitable for field- and factory wiring. Input Output DC-OK-Signal Type Screw termination Screw termination Push-in termination Solid wire Max. 6mm Max. 6mm Max. 1.5mm Stranded wire Max.
  • Page 23: Lifetime Expectancy

    Power Supply PS1000-A6-24.5 Lifetime Expectancy Lifetime Expectancy The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification.
  • Page 24: Mtbf

    Power Supply PS1000-A6-24.5 MTBF MTBF MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
  • Page 25: Emc

    Power Supply PS1000-A6-24.5 The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light industry environments. The device is investigated according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
  • Page 26: Environment

    Power Supply PS1000-A6-24.5 Environment Environment Operational temperature -25°C to +70°C (-13°F to 158°F) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the unit. Storage temperature -40°C to +85°C (-40°F to 185°F) For storage and transportation Output de-rating 1.6W/°C...
  • Page 27 Power Supply PS1000-A6-24.5 Environment Allowed Output C urrent at 24V Altitude 2000m 5000m 110kP a 80kP a 54kP a *) Atmos pheric press ure Figure 18.2 Output current vs. altitude...
  • Page 28: Safety And Protection Features

    Power Supply PS1000-A6-24.5 Safety and Protection Features Safety and Protection Features Isolation resistance Min. 500MOhm At delivered condition between input and output, measured with 500Vdc Min. 500MOhm At delivered condition between input and PE, measured with 500Vdc Min. 500MOhm At delivered condition between output and PE, measured with 500Vdc Min.
  • Page 29: Dielectric Strength

    Power Supply PS1000-A6-24.5 Dielectric Strength Dielectric Strength The output voltage is floating and has no ohmic connection to the ground. The output is insulated to the input by a double or reinforced insulation. Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down).
  • Page 30: Approvals And Fulfilled Standards

    Power Supply PS1000-A6-24.5 Approvals and Fulfilled Standards Approvals and Fulfilled Standards UL 61010-2-201 UL Certificate (former UL 508) Listed equipment for category NMTR - UL 61010-2-201 Electrical Equipment for Measurement, Control and Laboratory Use - Particular requirements for control Ind. Cont. Eq.
  • Page 31: Regulatory Compliance

    Power Supply PS1000-A6-24.5 Regulatory Compliance Regulatory Compliance EU Declaration of Conformity Trade conformity assessment for Europe The CE mark indicates conformance with the European • ATEX directive • EMC directive • Low-voltage directive (LVD) • RoHS directive REACH Directive Manufacturer's Statement...
  • Page 32: Physical Dimensions And Weight

    Power Supply PS1000-A6-24.5 Physical Dimensions and Weight Physical Dimensions and Weight Width 32mm, 1.26 inch Height 124mm, 4.88 inch Depth 102mm, 4.02 inch The DIN mounting rail height must be added to the unit depth to calculate the total required installation depth.
  • Page 33: Accessories

    Power Supply PS1000-A6-24.5 Accessories Accessories PS1000-D2-24.20.RM – Redundancy Module with Automated Load Sharing The redundancy module is a dual redundancy module, which can be used to build 1+1 redundant systems. The device is equipped with two input channels, each rated for 10A for ambient temperatures up to +70°C and are...
  • Page 34: Application Notes

    Power Supply PS1000-A6-24.5 Application Notes Application Notes 25.1 Peak Current Capability The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents. This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil.
  • Page 35 Power Supply PS1000-A6-24.5 Application Notes Output Voltage 10.5V 12ms Output C urrent 10ms /DIV Figure 25.3 15A peak current for 12ms , typ. (3x the nominal current) Note The DC-OK relay triggers when the voltage dips more than 10% for longer than 1ms.
  • Page 36 Power Supply PS1000-A6-24.5 Application Notes 25.2 Charging of Batteries The power supply can be used to charge lead-acid or maintenance free batteries. Two 12V SLA or VRLA batteries are needed in series connection. Charging Batteries Set the output voltage, measured at no load and at the battery end of the cable, very precisely to the end-of-charge voltage, see table below.
  • Page 37 Power Supply PS1000-A6-24.5 Application Notes 25.4 Parallel Use to Increase Output Power Devises can be paralleled to increase the output power. The output voltage shall be adjusted to the same value (±100mV) with the same load conditions on all devices, or the devices can be left with the factory settings.
  • Page 38 Power Supply PS1000-A6-24.5 Application Notes 25.5 Parallel Use for Redundancy 1+1 Redundancy Devices can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one device fails.
  • Page 39 Power Supply PS1000-A6-24.5 Application Notes Wiring examples: Load Output Output S hare Input Input 24V,5A 24V,5A Warning Load S hare DC - DC - R edudnadcy F ailure P ower P ower PS1000-D2- S upply S upply YR 20.246 Monitor 24.20.RM...
  • Page 40 Power Supply PS1000-A6-24.5 Application Notes 25.6 Two Phases Operation The power supply can also be used on two-phases of a three-phase-system. Such a phase-to-phase connection is allowed as long as the supplying voltage +10% is below 240V Ensure that the wire, which is connected to the N-terminal, is appropriately fused.
  • Page 41 Power Supply PS1000-A6-24.5 Application Notes OUTP UT Allowed O utput C urrent at 24V P ower 3.8A S upply INP UT +70°C Ambient T emperature Figure 25.9 Mounting orientation A (standard orientation) Allowed O utput C urrent at 24V +70°C Ambient T emperature Figure 25.10 Mounting orientation B (upside down)
  • Page 42 Pepperl+Fuchs Quality Download our latest policy here: www.pepperl-fuchs.com/quality www.pepperl-fuchs.com © Pepperl+Fuchs · Subject to modifications Printed in Germany DOCT-7302...