Output - Pepperl+Fuchs PS1000-A6-12.16 Technical Information

Table of Contents

Advertisement

Power Supply PS1000-A6-12.16

Output

8
Output
Output voltage
Adjustment range
Factory settings
Line regulation
Load regulation
Ripple and noise voltage
Output current
Overload behaviour
Short-circuit current
Output capacitance
1
Power boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
2
Hiccup mode
At heavy overloads (when output voltage falls below 6.5V), the power supply delivers continuous output current for 2s.
After this, the output is switched off for approx. 18s before a new start attempt is automatically performed.
This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally.
See Figure 8.3
3
Discharge current of output capacitors is not included.
Nom.
12Vdc
Min.
12-15Vdc
Max.
16.5Vdc
Typ.
12.0Vdc ±0.2%
Max.
10mV
Max.
50mV
Max.
50mVpp
1
Nom.
19.2A
Nom.
16A
Nom.
12A
1
Nom.
15.4A
Nom.
12.8A
Nom.
9.6A
Typ.
48A
Continuous current
2
Hiccup mode
3
Min.
20.5A
3
Max.
25.5A
Max.
7.3A
Min.
50A
Typ.
55A
Typ.
5 350µF
Guaranteed value
This is the maximum output voltage which can
occur at the clockwise end position of the
potentiometer due to tolerances. It is not a
guaranteed value which can be achieved.
At full load and cold unit
Between 85 and 300Vac
Between 0 and 19.2A, static value, see Figure 8.1
Bandwidth 20Hz to 20MHz, 50Ohm
At 12V and an ambient temperature below 45°C,
see Figure 19.1
At 12V and 60°C ambient temperature,
see Figure 8.1
At 12V and 70°C ambient temperature,
see Figure 19.1
At 15V and an ambient temperature below 45°C,
see Figure 19.1
At 15V and 60°C ambient temperature,
see Figure 8.1
At 15V and 70°C ambient temperature,
see Figure 19.1
For minimal 12ms once every five seconds,
see Figure 8.2.
The output voltage stays above 10V.
See chapter 27.1 for more peak current
measurements. For AC 100V mains, the pulse
length is shorter than 12ms.
Output voltage above 6.5Vdc, see Figure 8.1
Output voltage below 6.5Vdc, see Figure 8.1
Load impedance <30mOhm, see Figure 8.3
Load impedance <30mOhm, see Figure 8.3
Average (R.M.S.) current, load impedance
50mOhm, see Figure 8.3
Up to 12ms, load impedance <30mOhm,
see Figure 8.2
Up to 12ms, load impedance <30mOhm,
see Figure 8.2
Included inside the power supply
13

Advertisement

Table of Contents
loading

Table of Contents