Equipment Noise; Unit Sticks In Cycle - Kinetico Commercial Plus Series Technical Manual

Table of Contents

Advertisement

Equipment Noise

Problem
1. The unit makes a
squealing noise.
2. The unit makes a
gurgling, hissing or
bubbling sound.

Unit Sticks in Cycle

Problem
1. The unit sticks in
regeneration or
backwash cycle.
2. The unit sticks in
service cycle.
December 15, 2004
Rev. 3
Reason
The control disc is not flat on the ceramic,
causing the drain valve to flutter.
On new installations, there may be some
air trapped in the unit initially.
Air is being drawn into the plumbing.
The brine line and/or the brine valve are
not air checking.
Reason
The regeneration flow path is plugged at
the regeneration nozzle or flow control.
The regeneration drive pawl and/or spring
is weak or broken.
There is a damaged tooth on the control
disc.
The eccentric pinion is worn.
On backwashing filters, low pressure or
poor backwashing may cause a plugged
bed.
The regeneration start pawl is broken or
missing.
The control disc has a worn or missing
tooth.
General Information
CP Series Technical Manual
Solution
Replace the control disc,
balance piston spring and the
balance piston O-ring. You
may also want to change the
drain valves and seals.
Run through an entire cycle
to allow the air to escape.
Identify air leaks in the
plumbing and fix them.
Identify and replace the faulty
part(s).
Solution
Clean the regeneration flow
path.
Replace the regeneration
drive pawl.
Replace the control disc.
Replace the eccentric pinion
(snap fit).
Increase inlet pressure or the
frequency of backwash. Unit
may need re-bedding.
Replace or install
regeneration start pawl.
Replace control disc.
Page - 31