6.3 Scale Conversion Function

6.3 Scale Conversion Function

Overview of the function
● This function is to scale-convert values to an easy-to-use analog output range.
● When the minimum value and the maximum value are set in advance, D/A conversion is
made in the range between the minimum and maximum values as the full scale.
● Scale conversion processing is executed on a channel-by-channel basis.
Scale conversion processing
Voltage output range: Scale conversion when the input range of 0 to +5 V is converted to a
scale between the minimum value of 0 and the maximum value of +10,000
● The output value ranges from the minimum scale value -2% to the maximum scale value +2%.
● If data is outside this range, scale conversion will be disabled. The value equivalent to the
minimum scale value -2% or the value equivalent to the maximum scale value +2% will be
converted and output as an analog value.
Analog_4OUT parameters
Name
Scale conversion
Scale conversion
max value
Scale conversion
min value
6-6
Default
Setting range and description
Disable
Select "Enable".
Set the maximum value after scale conversion is executed.
10000
-32768 to +32767
Set the minimum value after scale conversion is executed.
0
-32768 to +32767