6.3 Scale Conversion

Overview of functions
• This function makes it possible to set an easy-to-use analog output range. Analog input
data acquired in a range between preset minimum and maximum values is scale converted
and stored in the I/O area. This function is convenient if used for scale unit conversion.
• Scale conversion is executed on a channel-by-channel basis.
• Conversion values read from the analog input unit include fractions. Therefore, convert the
values to easy-to-handle figures if needed.
(K)
25000
12500
1
Configuration
Name
Function
Scale
setting
conversion
Minimum value
of scale conversion
Maximum value
of scale conversion
* If data outside the minimum or maximum scale is input, scale conversion will be disabled and the minimum or
maximum scale value will be stored as a conversion value.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Scale
conversion
(V)
3
5
Default
Setting range and description
Not
Select "Execute."
execute
K0
Set the minimum value at the time of using the scale conversion
function.
Setting range: -30,000 to +30,000 (specified with a signed integer)
K10,000
Set the maximum value at the time of using the scale conversion
function.
Setting range: -30,000 to +30,000 (specified with a signed integer)
6.3 Scale Conversion
(K)
10000
5000
1
3
(V)
5
6-7