Item
Scale conversion settings
Offset / Gain settings
Analog output hold
(in STOP mode)
(Note 1)
The full scale (F.S.) on the accuracy of an analog voltage output range from +1 to +5 V and that of an
analog current output range from +4 to +20 mA are 0 to +5 V and 0 to +20 mA, respectively.
(Note 2)
When a value exceeding the rated value ±2% is set, the output is rounded to a value equivalent to the
rated value ±2%.
WUME-GM1AIO-01
Specifications
A desired value within the digital input range can be set for the scale
conversion setting value.
Setting range: -32768 to +32767
A desired value within the digital input range can be set for the offset
value.
Setting range: -3,000 to +3,000
A desired value within the digital input range can be set for the gain value.
Setting range: +9,000 to +11,000 (90% to 110%)
A desired output value while in STOP mode can be set as a digital value.
Setting range: -32640 to +32640
10.2 Performance Specifications