Chapter 9. Management switch maintenance procedures
(optional)
Procedures for replacing the Lenovo ThinkAgile CP management switch.
Note: A dedicated out-of-band management switch is required for this solution. If the Lenovo ThinkSystem
NE0152T RackSwitch is not used, you must provide an out-of-band management switch with the correct
configuration. Disregard this procedure if you are not including the Lenovo NE0152T as the management
switch in your solution.
Refer to Chapter 2 "Roles and responsibilities" on page 5 to determine who can perform these procedures.
For information about the terms of the warranty, visit
https://datacentersupport.lenovo.com/us/en/
.
warrantylookup

Hardware management network cable replacement

This section describes how to replace a hardware management network cable.
Procedure performed by: Customer or field service
When replacing cables that connect any Baseboard Management Controller (BMC) from the compute
enclosure, storage controllers, or the primary interconnect-dedicated port to the management switch, you
are required to unplug all hardware management network cables and then plug back into the management
switch to initiate a DHCP renewal. This operation can be done live without any specific pre- or post-steps.
During this operation, the hardware management network, the storage HA feature, and hardware detection
functionality are unavailable. Hardware-related statistics also cannot be retrieved.

Replace the management switch

Procedure performed by: Customer or field service
If during the installation, the customer performs specific configuration within the current Management
Switch, such as creating a network segmentation for the ThinkAgile CP hardware management network, this
configuration needs to be ported to the newly installed Management Switch before plugging the cables back.
Step 1.
If the power cord retention clip is installed, remove it:
85
© Copyright Lenovo