NOTE: After an offset signal, the new Remote Current Limit
may be viewed on the Remote EMS Limiting Dis-
play under the % Motor Current Key (See Section
3.5). However, if this display is being viewed when
the reset pulse occurs, the setpoint will not change
on the display. To view the new offset, first press
any other display key on the keypad and then press
the Remote EMS Limiting Display.
NOTE: Remote EMS Reset will not operate when a
Remote Control Center Option Kit is connected
to the micro. The Remote Control Center will
always determine the setpoint.
NOTE: Wiring from remove “dry” contact (for reset func-
tions) should not exceed 25 ft. and should never
be run in grounded conduit that does not carry
any wiring other than control wiring or in
screened cable. If an inductive device (relay,
contactor) is supplying these contacts, the coil
of the device must be suppressed with a sup-
pressor YORK Part Number 031-00808-000 (60
Hz models) or a standard RC suppressor (50
Hz models) across the inductive coil
NOTE: After an offset signal, the new Remote Setpoint
may be viewed on the Remote Reset Tempera-
ture Range display. However, if this display is
being viewed when the reset pulse occurs, the
setpoint will not change on the display. To view
the new offset, first press any other display key
on the keypad and then press the Remote Re-
set Temperature Range key. The new setpoint
will then appear.
NOTE: Remote Setpoint Reset will not operate when a
Remote Control Center Option Kit is connected
to the micro. The Remote Control Center will
always determine the setpoint.
NOTE: Wiring from remote “dry” contact (for reset func-
tions) should not exceed 25 ft. and should be
run in grounded conduit that does not carry any
wiring other than control wiring or in screened
cable. It an inductive device (relay, contactor)
is supplying these contacts, the coil of the de-
vice must be suppressed with a suppressor
YORK Part Number 031-00808-000 (60 Hz
models) or a standard RC suppressor (50 Hz
models) across the inductive coil.