York Millennium YDAS 410 Installation Operation & Maintenance page 101

Air cooled screw liquid chillers air cooled screw hermetic
Table of Contents

Advertisement

SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
SYSTEM 2 DATA
COMPRESSOR STATUS
RUN TIME
AVERAGE MTR = 0
PHASE L1 MTR = 0
PHASE L2 MTR = 0
PHASE L3 MTR = 0
DIFF OIL PRESSURE
SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
SYSTEM 3 DATA
COMPRESSOR STATUS
RUN TIME
AVERAGE MTR = 93
PHASE L1 MTR = 93
PHASE L2 MTR = 93
PHASE L3 MTR = 93
DIFF OIL PRESSURE
SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
ISN OPTION ENABLED
SOFTWARE VERSION C.A12.03.01
SAFETY SHUTDOWN NUMBER 3
SHUTDOWN @ 3:33PM
SYS 1 HIGH DSCH TEMP SHUTDOWN
SYS 2 STATUS: NO FAULTS
SYS 3 STATUS: NO FAULTS
RETURN WATER TEMP
LEAVING WATER TEMP
LOW WATER CUTOUT
COOLING RANGE
TARGET TEMP
61.3
PSIG
35.1 DEGF
55.0 DEGF
19.9 DEGF
221.8
PSIG
107.5 DEGF
229.2 DEGF
228.0 DEGF
ON
2
OFF
ON
ON
OFF
0– 0– 0– 0 D-H-M-S
0
%FLA
0
%FLA
0
%FLA
0
%FLA
0.0
PSID
62.2
PSIG
35.2 DEGF
37.0 DEGF
1.8 DEGF
92.8
PSIG
55.1 DEGF
56.0 DEGF
180.4 DEGF
OFF
OFF
OFF
OFF
ON
ON
0– 0– 0– 0 D-H-M-S
47
%FLA
47
%FLA
48
%FLA
46
%FLA
2.9
PSID
60.8
PSIG
34.9 DEGF
54.0 DEGF
19.1 DEGF
210.5
PSIG
104.8 DEGF
125.9 DEGF
122.3 DEGF
OFF
2
OFF
ON
ON
01 OCT 96
49.6 DEGF
44.7 DEGF
36.0 DEGF
41.0 TO 44.6 DEGF
42.8 DEGF