CAUTION:
No Controls (relays,
etc.)
should
be
mounted in the Smart
Panel enclosure or con-
nected to power sup-
plies in the control
panel. Additionally, con-
trol wiring not con-
nected to the Smar t
Panel should not be run
through the cabinet.
This could result in nui-
sance faults.
CAUTION:
Any inductive devices
(relays) wired in series
with the flow switch for
star t/stop, into the
Alarm circuitry, or pilot
relays for pump starters
wired through motor
contactor auxiliary con-
tacts must be sup-
pressed with YORK
P/N 031-00808-000
suppressor across the
relay/contactor coil
which activates the
contacts.
Any contacts con-
nected to flow switch
inputs or BAS inputs on
terminals 13 - 19 or
TB3, or any other ter-
minals, must be sup-
pressed with a YORK P/
N 031-00808-000 sup-
pressor across the re-
lay/contactor coil which
activates the contacts.
CAUTION:
Control wiring con-
nected to the control
panel should never be
run in the same conduit
with power wiring.
CONTROL POWER SUPPLY
CONTROL
UNIT
POWER
VOLTAGE
SUPPLY
ALL MODELS
115-1-50/60
W/O TRANS.
MODELS
-17
200-1-60
WITH
-28
230-1-60
TRANS.
-46
400-1-60
*
- 5 8
575-1-60
* All primary and secondary wiring between transformer and control panel included.
MAX
NON-
MIN
DUAL
FUSED
CIRCUIT ELEMENT
DISC.
AMP.
FUSE
SWITCH
SIZE
SIZE
20A
20A 250V
30A 240V
15A
15A 250V
30A 240V
15A
15A 250V
30A 240V
8A
8A 600V
30A 480V
8A
8A 600V
30A 600V
LD03687