NOTE: A Control Range (CR) selection that is too small
for the application will result in excessive com-
pressor cycling or hunting of the compressor
slide valves. If this situation occurs, leaving
chilled liquid temperature may vary consider-
ably. It is recommended that a CR of less than
3.0°F be avoided. Increase the CR as needed
to reduce cycling and hunting.
Subordinate
NOTE: Remember to program the Mixed Target tem-
perature to a slightly higher value than the Panel
Target temperature.
NOTE: Failure to press the Enter key will cause the
newly programmed values to be ignored and
not entered into memory.