AMBIENT AIR TEMP
LOW AMBIENT CUTOUT
LOW PRESSURE CUTOUT
LEAD SYSTEM
LOCAL REMOTE SETTING:
SYSTEM 1 DATA
COMPRESSOR STATUS
RUN TIME
AVERAGE MTR = 138
PHASE L1 MTR = 145
PHASE L2 MTR = 141
PHASE L3 MTR = 127
DIFF OIL PRESSURE
SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
SYSTEM 2 DATA
COMPRESSOR STATUS
RUN TIME
AVERAGE MTR = 94
PHASE L1 MTR = 99
PHASE L2 MTR = 93
PHASE L3 MTR = 91
DIFF OIL PRESSURE
SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
SYSTEM 3 DATA
COMPRESSOR STATUS
RUN TIME
AVERAGE MTR = 0
PHASE L1 MTR = 0
PHASE L2 MTR = 0
PHASE L3 MTR = 0
DIFF OIL PRESSURE
SUCTION PRESSURE
SATURATED SUCTION
SUCTION TEMP
SUPERHEAT
DISCHARGE PRESSURE
SATURATED DISCHARGE
DISCHARGE TEMP
OIL TEMP
LIQUID INJECTION VALVE
FORWARD FANS
REVERSE FANS
LIQUID LINE SOLENOID
RUN PERMISSIVE
70.0 DEGF
25.0 DEGF
44.0
PSIG
SYS 1
LOCAL
ON
0- 0- 11- 1 3 D-H-M-S
74
%FLA
78
%FLA
76
%FLA
68
%FLA
3.0
PSID
59.9
PSIG
31.8 DEGF
46.9 DEGF
15.1 DEGF
181.5
PSIG
94.5 DEGF
232.2 DEGF
215.5 DEGF
ON
2
OFF
ON
ON
ON
0– 0– 3– 52 D-H-M-S
47
%FLA
48
%FLA
47
%FLA
46
%FLA
2.0
PSID
60.9
PSIG
33.9 DEGF
42.9 DEGF
9.0 DEGF
171.8
PSIG
90.5 DEGF
211.5 DEGF
188.3 DEGF
ON
2
OFF
ON
ON
OFF
0– 0– 0– 0 D-H-M-S
0
%FLA
0
%FLA
0
%FLA
0
%FLA
0.0
PSID
78.2
PSIG
46.1 DEGF
48.2 DEGF
2.1 DEGF
157.0
PSIG
85.1 DEGF
86.2 DEGF
100.1 DEGF
OFF
OFF
OFF
OFF
ON

Advertisement