NOTE: Never bypass a flow switch. This will cause
damage to the chiller and void any warranties.
NOTE: Wiring from remote “dry” contacts (for stop/start
reset functions) should not exceed 25 ft. and
should be run in grounded conduit that does
not carry any wiring other than control wiring or
in screened cable. If an inductive device (relay,
contactor) is supplying these contacts, the coil
of the device must be suppressed with a sup-
pressor YORK Part Number 031-00808-000 (60
Hz models) or a standard RC suppressor (50
Hz models) across the inductive coil.