Contec F&eIT Series User Manual page 17

I/o controller module
Hide thumbs Also See for F&eIT Series:
Table of Contents

Advertisement

2. Module Nomenclature and Settings
Names and Functions [Common]
Table 2.1. Names and Functions
Name
Status LED
RUN
STATUS
LAN LED
LINK
Power/RX [CPU-CA10(FIT)GY]
ACT [CPU-CA20(FIT)GY]
Setting switch
Group ID setup
switch: Unit ID
setup switch:
RESET SW
Manual reset
ERROR OUT *2 External output contacts, such as Power
OFF
and Link disconnection, for abnormal
conditions
UTP port
10BASE-T LAN connect [CPU-
CA10(FIT)GY]
10/100BASE-TX LAN connect
[CPU-CA20(FIT)GY]
*1 Group ID "A" (standalone boot mode) can only be used on the CPU-CA20(FIT)GY.
If the Group ID is set to "A", the Unit ID is set in the range 0 - 7Fh by software.
*2 Only on the CPU-CA10(FIT)GY.
10
Function
:0 - F
:0 - 7
Settings & Indicator
Refer to Table 2.2. Operating Modes and Status
Indicators
OFF : Not connected
ON : Connected to the LAN
OFF : Power off
ON : Power on
Flashing: Receiving data
OFF : Communication inactive
ON : Communication active
Group ID : 0 - 8, A *1
0 - 7 : Assist Server connect mode
8 : Stand-alone startup mode
A : Stand-alone startup mode *1
9, B - D : Not used
E is used for V.UP (upgrading) and system recovery
mode.
F : Default initialization mode
Unit ID : 0 - 7 *1
---
---
---
CPU-CA10(FIT)GY, CPU-CA20(FIT)GY

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpu-ca10fitgyCpu-ca20fitgy

Table of Contents