1. Technical Specifications
Product type
Dual sense motion sensor ( HF and PIR, Tri-level control )
Operating voltage
120~277VAC 50/60Hz
Rated load
Capacitive: 400VA@120V; 800VA@220~277V
Resistive: 700W@120V; 1600W@220~277V
Power consumption
< 1W
o
Detection angle
360
Installation Height : 6m
Detection area (Max.)*
Detection Range (Ø) :12m
Detection range
10% / 50% / 75% / 100%
Hold time
2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time
0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞
Stand-by dimming level
10% / 20% / 30% / 50%
Daylight threshold
2 ~ 500Lux, Disable
Warmming up time
30s
o
Operating temperature
-20
C ~ +55
Sensor mode
PIR, HF, PIR+HF, PIR / HF
3. Rotary Switch Settings
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Detection
Hold
Channel
range
time
0
100%
5s
1
100%
1min
2
100%
5min
3
100%
5min
4
100%
5min
5
100%
5min
6
100%
5min
7
100%
10min
8
100%
10min
9
100%
10min
A
100%
10min
B
75%
10min
C
50%
10min
D
100%
30min
E
100%
30min
F
100%
5s
Note: settings can also be changed by remote control HRC-11. The last action controls.
4. Sensor Mode Selection
Sensor mode can be easily selected by choosing the correct combination of the DIP switches
(see table below):
1 2
I
II
III
IV
Installation and Instruction Manual
o
C
Rotary switch preset (Please
see the location in 2. Installation)
Stand-by
Stand-by
time
dimming level
10s
10%
5min
10%
10min
10%
30min
10%
0s
Disable
+∞
10%
+∞
30%
10min
10%
30min
10%
+∞
10%
+∞
30%
+∞
10%
+∞
10%
+∞
10%
+∞
30%
10s
10%
HF+PIR: Light is on when both HF
and PIR sensors are activated.
HF
PIR
HF/PIR: Light is on when HF or PIR
HF+PIR
sensors are activated.
HF/PIR
2. Installation
Warnings:
1. Installation must be carried out by a
qualified engineer in accordance with
local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
cause mis-triggering.
4. Ensure environmental conditions are
suitable for electronic equipment
Note: the blinds are optional, they may be inserted behind the lens for focussing the detection range.
56
Note:We recommend the mounting distance between sensor to sensor
should be more than 2m to prevent sensors from false-triggering.
Direct junction "J" box mounting
a. Separate control board (A) from facia (B)
& junction box (C).
b. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box (C).
Daylight
threshold
d. Set-up sensor modes as per sections 3 & 4
of this manual.
Disable
e. Clip facial plate (B) to control board (A).
2Lux
10Lux
30Lux
10Lux
30Lux
Disable
2Lux
10Lux
30Lux
Disable
30Lux
10Lux
50Lux
Disable
2Lux
5. Wiring Diagram
L
N
P
L'N N L
HIM11
1-10V
-
* Note: if neither function 5.2 nor 5.3 is desired, simply leave the "push" terminal disconnected.
Infrared receiver
HF Sensor module
Blind
A
Rotary switch preset
Blind
B
Surface mount assembly
a. Separate control board (A) from facia (B) &
Surface box (C).
b. Securely mount surface box (C) to a flat and
solid surface.
c. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).
C
56
A
B
+
-
L N
LED
LED driver
Max. 800W
+
1-10V
+
-
C - Surface box
B - Facia Cover
PIR
Photocell
LED indicator
Sensor mode selection
A - Control Board
C
56
A
B
+
-
L N
LED
LED driver
+
1-10V
-
HIM11-20190104-A1
Need help?
Do you have a question about the DualSense HIM11 and is the answer not in the manual?
Questions and answers