6 Electrical connection

DANGER
!
Risk of fatal injury due to electric shock.
Î For electrical installation, observe the
relevant electrotechnical regulations and
the accident prevention regulations that
apply in the country of use.
Valid regulations in Germany:
− VDE regulations
− Accident prevention regulations of the
employers' liability insurance.
DANGER
!
Risk of fatal injury due to the formation of
an explosive atmosphere.
Î For installation in hazardous areas,
observe the relevant standards that apply
in the country of use.
Valid standards in Germany:
− EN 60079-14: 2008 (VDE 0165,
Part 1) Explosive Atmospheres –
Electrical Installations Design, Selection
and Erection.
WARNING
!
Incorrect electrical connection will render
the explosion protection unsafe.
Î Adhere to the terminal assignment.
Î Do not undo the enameled screws in or
on the enclosure.
EB 3963 EN
WARNING
!
Intrinsic safety rendered ineffective in
intrinsically safe devices.
Î Only connect intrinsically safe devices
intended for use in intrinsically safe
circuits to certified intrinsically safe input-
connected units.
Î Do not place intrinsically safe devices
back into operation that were connected
to intrinsically safe input-connected units
without certification.
Î Do not exceed the maximum permissible
electric values specified in the EC type
examination certificates when
interconnecting intrinsically safe electrical
equipment (U
or U
i
or C
and L
or L
0
i
Selecting cables and wires
Î Observe clause 12 of EN 60079-14:
2008 (VDE 0165, Part 1) for installation
of the intrinsically safe circuits.
Î Clause 12.2.2.7 applies when running
multi-core cables and wires with more
than one intrinsically safe circuit.
Î Preferably use connecting lines with
minimum 0.5 mm² conductor cross-
section and 6 to 12 mm outside
diameter.
Î Radial thickness of the insulation of a
conductor for common insulating
materials (e.g. polyethylene): minimum
0.2 mm.
Î Diameter of an individual wire in a fine-
stranded conductor: minimum 0.1 mm.
Electrical connection
, l
or I
, P
or P
0
i
0
i
0
).
0
, C
i
53