620 series ANSI
Communication Protocol Manual
Vendor-specific implementation

DNP3 link modes

Serial and TCP/IP modes are available. They are mutually exclusive.

DNP3 data objects

The DNP3 protocol in 620 series IEDs is built on top of the internal IEC 61850 data model.
Thus, the DNP3 application data objects and Class events are derived from IEC 61850
data objects and data set reporting. The 620 series IEDs have a predefined IEC 61850 data
set configuration. In other words, it is predefined which internal data object changes the
620 series IEDs detect.
The available DNP3 data objects in the 620 series IEDs are selected from the objects
predefined in the IEC 61850 data sets. IEC 61850 data set reporting and DNP3 Class event
reporting are basically identical.
For a list of the available data objects, see the point list manual.

DNP3 serial link mode

DNP3 serial can be assigned to a serial communication port in the IED. Serial
communication ports are named COM1...COMn, depending on how many serial ports the
620 series IED hosts.
If this protocol does not operate as expected, check that other serial
protocols are not using the COM port also.
DNP3 protocol ignores any parity setting in the COM settings group;
DNP3 is defined as an 8 bit/no parity protocol with a 16-bit CRC every 16
bytes. This provides better error detection than parity.
Vendor-specific implementation
Section 3
11