Danfoss VLT CDS 803 Operating Manual page 30

Compressor drive 6–30 kw
Hide thumbs Also See for VLT CDS 803:
Table of Contents

Advertisement

VLT® Compressor Drive CDS 803
Operating Guide
Fault
Fault text
number
46
Gate drive voltage
fault
47
24V supply low
49
Speed limit
50
AMA calibration
51
AMA check
U
,I
nom
nom
52
AMA low,I
nom
53
AMA big motor
54
AMA small mot
55
AMA par. range
56
AMA interrupt
57
AMA timeout
58
AMA internal
59
Current limit
60
External interlock
66
Heat Sink Tempera-
ture Low
69
Pwr. Card Temp
80
Drive initialised
87
Auto DC Braking
95
Broken belt
96
Start delayed
97
Stop delayed
30 | Danfoss A/S © 2021.06
Warn-
Alarm
Trip
ing
locked
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
(3)
X
X
X
X
X
X
X
(2)
(2)
X
X
Cause of problem
The supply on the power card is out of range.
24 V DC may be overloaded.
The compressor runs at a speed lower than specified in pa-
rameter 1-87 Compressor Min Speed for Trip [Hz].
AMA calibration failed
Motor voltage, current and power configured wrong in pa-
rameters.
Motor current too low.
Motor is too large for the AMA to be performed.
Motor is too small for the AMA to be performed.
Parameter values found is outside of the acceptable range.
The AMA is interrupted by user.
The AMA takes too long time to complete.
Contact the local Danfoss supplier.
The current is higher than the value in parameter 4-18 Current
Limit.
External interlock has been activated. To resume normal oper-
ation, apply 24 V DC to the terminal programmed for external
interlock and reset the drive (via serial communication, digital
I/O, or by pressing [Off/Reset]).
This warning is based on the temperature sensor in the IGBT
module.
The internal temperature has exceeded the allowed operating
boundary. Check that the ambient operating temperature is
within the limits. Check the fan operation.
All parameter settings are initialized to default settings.
The drive is auto DC braking.
The torque is below the torque level set for no load indicating
a broken belt.
Power to the drive has been on for a shorter time than speci-
fied in parameter 28-01 Interval Between Starts twice.
Stopping the motor has been delayed due to short cycle pro-
tection being active.
AQ321748767627en-000301 / 130R0570