5.6   Top Cover Installation and Extension Test
This procedure provides instructions for installing the top cover and performing an enclosure extension test
for an Ultrastar Serv60+8 .
Before you begin: Complete the instructions in
Table 40: Installation Requirements
Tool(s): Long T15 Torx Screwdriver
Part(s): N/A
Person(s): 1
Time: 5 minutes
Step 1 : Secure the chassis top cover to the rack using the captive M5 thumb-screws as shown in the
following image. Use a T15 Torx screwdriver, and tighten the screws to 3.38-3.61 Nm / 30-32 in-
lbf.
Figure 38: Cover Retention Screws
Step 2 : Now that the chassis is installed, test the installation by sliding the enclosure in and out of the
rack a minimum of three times. If the enclosure binds, catches, or displays any incorrect motion
or behavior repeat the installation.
Step 3 : Grasp both handles at the front of the enclosure and pull with even pressure to extend the
chassis out of the rack until it is stopped by the safety latches. The safety latches will prevent the
enclosure from coming out of the rack completely and the cover will remain in the rack attached
to the rear alignment brackets.
Note: Adjustments of the vertical rack rails may be required to fix any issues that
may occur.