Commissioning - Maico ER-AP Installation And Operating Instructions Manual

Surface-mounted exhaust air system for single-duct air extraction according to din 18017-3
Table of Contents

Advertisement

13 Commissioning

7. Slide fan insert evenly, in parallel, onto both
studs. Ensure that the two locking tabs of the
stud and the locking lever audibly engage so
that the fan insert is secure.
NOTICE Damage to the unit. Degree of protec-
tion is not guaranteed if in the wrong installa-
tion position.
Only fit upper part of housing with the Maico
name in the bottom right.
8. Attach upper part of housing and fasten with
central screw.
Upper part of housing can only be fitted in
one position. Ensure that the two arrows on
the upper part of the housing and the words
"exhaust socket" are facing the exhaust
socket.
9. Check that filter mat is fitted correctly.
10.Affix time strip (→ Title page) and push the ac-
tivation button all the way.
The red dye in the interior of the
bar [B] is released. The
bar indicator first fills
slightly. Within the
next 6 months, the bar
indicator [B] will rise to the
upper edge (indicator value 6).
11.Fit cover (MAICO name on bottom right). The
cover must audibly click into place.
20
13 Commissioning
1. Switch on mains fuse and remove warning
sign.
2. Run function test. To do this, switch unit on
and off, observe delay times (for control mod-
els Controls (circuit board types) [} 10]).
3. Check that the unit is running smoothly. It is
also important that the air can flow un-
hindered.
4. Switch off unit.
Operating the unit
Depending on model and connection variant, use
switches provided by customer to switch the unit
on and off. Barrier-free units do not need
switches. Alternative connection options are de-
scribed (Wiring diagrams [} 24]).
• Standard, VZ and G model: The unit is
switched on and off with switches that are to be
provided by the customer.
• F model: Barrier-free. The unit switches on
once the room lighting is activated. Can also be
operated manually with optional switch.
• H model: Barrier-free, no switch needed. Can
however also be operated manually with op-
tional switch.
If the unit is switched on and off manually,
function in accordance with relevant standards
is not always ensured.

Advertisement