3 Point lists
3.1 Binary Input Points
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Name
Index
ProtActive
120
Settings Calc.
121
Error Sum Alarm
122
Alarm Sum Event
123
Error A/D conv.
124
Relay PICKUP
125
Relay TRIP
130
Definitive TRIP
131
Emer. mode
135
3.1.9

Internal mode status

DataStop
136
Test mode
137
Chatter ON
138
Man.Clos.Detect
139
LOCKOUT
140
3.1.10

Setting group

Group A
149
Group B
150
Group C
151
Group D
152
3.1.11

User-allocated single-point indications

*
<unnamed>
153
<unnamed>
154
<unnamed>
155
<unnamed>
156
<unnamed>
157
<unnamed>
158
<unnamed>
159
<unnamed>
160
<unnamed>
161
<unnamed>
162
<unnamed>
163
<unnamed>
164
24
Description
At least one protection funct. is active; ON=1, OFF=0
Setting calculation is running; ON=1, OFF=0
Error with a summary alarm; ON=1, OFF=0
(ref. to chap. 1.1.1)
Alarm Summary Event; ON=1, OFF=0
(ref. to chap. 1.1.2)
Error A/D converter; ON=1, OFF=0
Relay PICKUP; ON=1, OFF=0
Relay GENERAL TRIP command; ON=1, OFF=0
Relay Definitive TRIP; ON=1, OFF=0
Energency mode; ON=1, OFF=0
Stop data transmission; ON=1, OFF=0
(ref. to chap. 1.1.3)
Test mode; ON=1, OFF=0
Chatter ON; ON=1, OFF=0
Manual close signal detected; ON=1, OFF=0
LOCKOUT is active; ON=1, OFF=0
Setting Group A; ON=1, OFF=0
Setting Group B; ON=1, OFF=0
Setting Group C; ON=1, OFF=0
Setting Group D; ON=1, OFF=0
User input 1
User input 2
User input 3
User input 4
User input 5
User input 6
User input 7
User input 8
User input 9
User input 10
User input 11
User input 12
Class
2
3
2
2
2
1
1
1
1
3
3
3
2
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
SIPROTEC, 7SD80, Bus mapping DNP 3.0