Pressure parameter
Rev. 0
Purge programs gas application:
Functions
Purge
phase
Ex_p_1
Gas
Yes
Ex_p_2
Gas
Yes
Ex_p_4
Gas
Yes
Ex_p_5
Gas
Yes
Ex p programs dust application:
Functions
Purge
phase
Ex_pD_1
Dust
No
Ex_pD_2
Dust
No
The system pressures of the Ex p equipment are defined in the "Pressure
parameter" submenu.
p4 = Maximum pressure, operation. Depending on the selection of the purge
program, there is a shutdown or message.
p5 = Maximum pressure, purge. Depending on the selection of the purge
program, there is a shutdown or message.
01-37A2-7D0001_px_Manual_Exp-Control-Unit_20210923_0_en.docx
Operation
Purge time starts
Purge time stops
when p3 is
when p5 is
exceeded
reached
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Purge time starts
Purge time stops
when p3 is
when p5 is
exceeded
reached
No
No
No
No
po = Operating pressure. Pressure
value at which control takes place
during the operating phase.
p1 = Minimum pressure. Shut-off
value; if the pressure falls below this
value, the enable is reset.
p2 = Pre-alarm. Value at which an
alarm can be given before shutdown.
p3 = Purge pressure. Purge time starts
when the set point is exceeded.
Ex p
Ex p active
inactive
after
after
Expiration
po < p1
purge time
po > p4
Expiration
po < p1
purge time
Expiration
po < p1
purge time
po > p4
Expiration
po < p1
purge time
Ex p
Ex p active
inactive
after
after
po < p1
po >= p1
po > p4
po >= p1
po < p1
Page 59 of 96