Combining Units And Options; Possible Options For The Indoor Unit - Daikin FXMA50A5VEB Installer And User Manual

Vrv system air conditioner
Hide thumbs Also See for FXMA50A5VEB:
Table of Contents

Advertisement

15
|
About the units and options

15.4 Combining units and options

15.4.1 Possible options for the indoor unit

Installer and user reference guide
46
e
a
c
a Indoor unit
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + transmission cable
g Drain pipe
INFORMATION
Certain options may NOT be available in your country.
Make sure you have the following mandatory options:
User interface: Only a safety system compatible user interface can be used. See
the technical data sheet for user interface compatibility (e.g. BRC1H52*)
Note: The user interface will generate a visible and audible warning in case of
refrigerant leakage detection. E.g., BRC1H52* user interfaces can generate an
alarm of 65  dB (sound pressure, measured at a distance of 1  m from the alarm).
Sound data is available in the technical data sheet of the user interface. The alarm
should always be 15 dB louder than the background noise of the room. In case of
higher background noise we recommend connecting an external alarm (field
supply) to the optional output PCB of the indoor unit. This field supplied alarm
must be mounted in every room where an indoor unit is installed.
CAUTION
Each indoor unit has to be connected to a separate user interface. Only a safety
system compatible remote controller can be used as the user interface. See
technical data sheet for remote controller compatibility (e.g. BRC1H52/82*).
The user interface has to be put in the same room as the indoor unit. For details,
please refer to the installation and operation manual of the user interface.
d
g
f
b
FXMA-A
VRV system air conditioner
4P680920-1 – 2022.01