Combining Units And Options; About Combining Units And Options; Possible Combinations Of Indoor Units; Possible Options For The Outdoor Unit - Daikin RXYSQ6T8VB Installer And User Manual

System air conditioner
Table of Contents

Advertisement

a
b
c
c
f
d
d
a
VRV IV-S Heat pump outdoor unit
b
Refrigerant piping
c
VRV direct expansion (DX) indoor unit
d
User interface (dedicated depending on indoor unit type)
e
BP box (required to connect Residential Air (RA) or Sky Air
(SA) direct expansion (DX) indoor units)
f
Residential Air (RA) direct expansion (DX) indoor units
g
User interface (wireless, dedicated depending on indoor
unit type)
4.5

Combining units and options

4.5.1

About combining units and options

NOTICE
To be sure your system setup (outdoor unit+indoor unit(s))
will work, you have to consult the latest technical
engineering data for VRV IV-S heat pump.
The VRV IV-S heat pump system can be combined with several
types of indoor units and is intended for R410A use only.
For an overview which units are available you can consult the
product catalogue for VRV IV-S.
An overview is given indicating the allowed combinations of indoor
units and outdoor units. Not all combinations are allowed. They are
subject to rules (combination between outdoor-indoor, combinations
between indoor units, etc.) mentioned in the technical engineering
data.
4.5.2

Possible combinations of indoor units

In general following type of indoor units can be connected to a VRV
IV-S heat pump system. The list is non-exhaustive and is depending
on both outdoor unit model and indoor unit model combinations.
▪ VRV direct expansion (DX) indoor units (air to air applications).
▪ SA/RA (Sky Air/Residential Air) direct expansion (DX) indoor units
(air to air applications). Further referred to as RA DX indoor units.
These indoor units require a BP box.
▪ AHU (air to air applications): EKEXV-kit+EKEQ-box are required,
depending on application.
▪ Aircurtain (air to air applications): CYV/CAV (Biddle) series,
depending on application.
INFORMATION
▪ Combination of VRV DX and RA DX indoor units is not
allowed.
▪ Combination of RA  DX and AHU indoor units is not
allowed.
▪ Combination of RA DX and aircurtain indoor units is not
allowed.
4.5.3

Possible options for the outdoor unit

INFORMATION
Refer to the technical engineering data for the latest option
names.
RXYSQ4~6T8V/YB
VRV IV-S system air conditioner
4P482277-1 – 2017.04
e
e
f
g
g
Refrigerant branching kit
Description
Refnet header
Refnet joint
For the selection of the optimal branching kit, please refer to
"5.3.4 To select refrigerant branch kits" on
Cool/heat selector
In order to control the cooling or heating operation from a central
location, the following option can be connected:
Description
RXYSQ4~6_V
Cool/heat selector
KRC19-26A
switch
Cool/heat selector
EBRP2B
PCB
Cool/heat selector
cable
With optional fixing
KJB111A
box for the switch
External control adaptor (DTA104A61/62)
To instruct specific operation with an external input coming from a
central control the external control adaptor can be used. Instructions
(group or individual) can be instructed for low noise operation and
power consumption limitation operation.
The external control adapter has to be installed in the indoor unit.
PC configurator cable (EKPCCAB)
You can make several commissioning field settings through a
personal computer interface. For this option EKPCCAB is required
which is a dedicated cable to communicate with the outdoor unit.
The
user
interface
software
www.daikineurope.com/support-and-manuals/software-downloads/.
5

Preparation

5.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the electrical wiring
5.2

Preparing installation site

Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit must be covered.
Choose the installation location with sufficient place for carrying the
unit in and out of the site.
5 Preparation
Model name
KHRQ22M29H
KHRQ22M20T
page 13.
RXYSQ4~6_Y
KRC19-26A
EKCHSC
KJB111A
is
available
on
http://
Installer and user reference guide