(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number
• —: Value number
: Default
FXMA-A
VRV system air conditioner
4P680920-1 – 2022.01
(a)
Only use in combination with optional remote sensor or when setting M 10 (20), SW 2, —
03 is used.
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room. It determines
the interval at which "Time to clean filter" notification is displayed on the user
interface.
If you want an interval of...
(air contamination)
±2500 h (light)
±1250 h (heavy)
Notification ON
Notification OFF
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller thermostat sensor
is used.
When the remote controller thermostat sensor
Used in combination with indoor unit thermistor
Not used (indoor unit thermistor only)
Used exclusively
Setting: Thermostat differential changeover (if remote sensor is used)
If the system contains a remote sensor, set the increase/decrease increments.
If you want to change increments to...
1°C
0.5°C
Setting: Differential for automatic changeover
Set temperature difference between cooling setpoint and heating setpoint in
automatic mode (availability depends on the system type). Differential is cooling
setpoint minus heating setpoint.
is...
20
Configuration
|
(1)
Then
M
SW
10 (20)
0
01
02
3
01
02
(1)
Then
M
SW
10 (20)
2
01
02
03
(1)
Then
M
SW
12 (22)
2
01
02
Installer and user reference guide