Samsung AM032MNQDCH/AA Service Manual page 224

System air conditioner indoor unit
Table of Contents

Advertisement

Troubleshooting
Option
SEG13
Explanation
Remote Controller
Display
Indication and Details
(*1) Height difference : The difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest
place.
For example, When the indoor unit is installed 40 m(131.23 ft) higher than the indoor unit installed at the lowest
place, select the option 1.
(*2) Distance : The difference between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe
length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40 m(131.23 ft) away
from an outdoor unit, select the option 2.
(100 m(328 ft) - 40 m(131.23 ft) = 60 m(196.85 ft))
(*3) Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to using
external heater
e.g. 1) Setting 02 series SEG9 =1 / Setting 05 series SEG18 = 0: Hot water heater is turned on at the same time as the heating ther-
mostat is on, and turned off when the heating thermostat is off.
e.g. 2) Setting 02 series SEG15 =2 / Setting 05 series SEG18 =A:
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 8.1 °F(4.5 °C) for 10 minutes.
Room temp. > set temp. + f(heating compensation temp.)
- External heater is turned off when the temperature is maintained as 8.1 °F(4.5 °C) + 1.8 °F(1 °C)
(1 °C is the Hysteresis for On/Off selection.)
4-24
SEG14
SEG15
SEG16
(*3)
SEG17
SEG18
Control variables when using hot water /
external heater
Indication
Set temp. for
heater On/Off
At the same
0
time as thermo
on
At the same
1
time as thermo
on
At the same
2
time as thermo
on
2.7 °F
3
(1.5 °C)
2.7 °F
4
(1.5 °C)
2.7 °F
5
(1.5 °C)
5.4 °F
6
(3.0 °C)
5.4 °F
7
(3.0 °C)
5.4 °F
8
(3.0 °C)
8.1 °F
9
(4.5 °C)
8.1 °F
A
(4.5 °C)
8.1 °F
B
(4.5 °C)
10.8 °F
C
(6.0 °C)
10.8 °F
D
(6.0 °C)
10.8 °F
E
(6.0 °C)
Samsung Electronics
Details
Delay time
for heater
On
No delay
10 minutes
20 minutes
No delay
10 minutes
20 minutes
No delay
10 minutes
20 minutes
No delay
10 minutes
20 minutes
No delay
10 minutes
20 minutes

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Am009fn1dch/aaAm012fn1dch/aaAm009fnndch/aaAm012fnndch/aaAm018fnndch/aaAm020fnndch/aa ... Show all