AGA Gas Installation Code AG601 - NZ 5261. • Any other relevant statutory regulation. • Rinnai strongly recommend that this product be installed with an • approved flue system for optimum product performance. This appliance must only be installed, serviced and removed by an •...
5. Under no circumstances must combustible materials be present on the inside of the fireplace recess or flueway. Note: A Rinnai Zero Clearance kit is available where the heater is required to be installed in close proximity to combustible framing.
There must be no leakage of smoke through the structure of the chimney during or after the test. Inside, upstairs and/or adjacent rooms should also be checked. If any of the above criteria is not met, a Rinnai approved flue liner system must be installed.
Page 4
FLUEING CHECK DIMENSIONS OF FIREPLACE • Check dimensions of fireplace and if necessary bring them to dimensions shown. Note. If the width of the fireplace is less than 700mm then provision needs to be made to run the gas supply outside of the fireplace cavity.
GAS CONNECTION RUN GAS SUPPLY • For pipe sizing, refer to your local gas installation codes. Copper supply should be run leaving a flared connection at the position shown. PURGE SUPPLY OF AIR AND SWARF. All foreign materials such as filings must be purged from the gas supply, as they may cause the gas valve to malfunction.
LOG INSTALLATION he logset is packed inside the heater and the packaging must be removed prior to installing the logset in its correct position. • Remove both side panels. • Remove fastenings on both sides of the top glass retainer. Lift retainer away from heater.
INSTRUCT CUSTOMER ON USE OF UNIT • Explain to customer about use and care of unit. Make sure the customer understands the instructions. EXPLAIN • Ignition, Adjusting heat level, Fan Switch, Turning “OFF”. NOTE: RINNAI RESERVES THE RIGHT TO CHANGE OR MODIFY SPECIFICATIONS WITHOUT NOTICE.
FGL31 ISBN (NG) Australia FGL31 ISBL (Propane) Australia IB30N (NG) New Zealand IB30L (Propane) New Zealand Description: Rinnai Inbuilt Radiant/Convector, glass-fronted, ceramic log space heater with forced convection and natural draught flue system. Input: 30 MJ/h Natural Gas and Propane. Gas Control: Rinnai Push-Button Combination Control.
INSTALLATION / COMMISSIONING CHECKLIST (To be completed by certified Gas Installer) ____________________ Model: 1. Was a fireplace inspection carried out? (ie. clearances, combustibles etc.) 2. Was chimney inspected? 3. Did chimney require flue liner system to be installed? If NO, did chimney meet specified criteria as per manual? 4.