Honeywell Silent Knight SK-Monitor Installation And Maintenance Instructions

Honeywell Silent Knight SK-Monitor Installation And Maintenance Instructions

Advertisement

Quick Links

inStallation anD maintenance inStructionS
SK-monitor module

SpecificationS

Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Max. IDC wiring resistance:
Maximum IDC Voltage:
Maximum IDC Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Before inStalling
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
general DeScription
The SK-Monitor Module is intended for use in intelligent, two-wire systems,
where the individual address of each module is selected using the built-in
rotary switches. It provides either a Class A or Class B fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator.
compatiBility requirementS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
figure 1. controlS anD inDicatorS:
mounting
The SK-Monitor mounts directly to 4-inch square electrical boxes (see Figure
2). The box must have a minimum depth of 2
trical boxes (SMB500) are available from Silent Knight.
SK-460-013
15 to 32 VDC
5.0 mA (LED on)
375µA (group poll), 350 µA (direct poll), 600 µAmps (communication, IDC shorted)
47K Ohms
1,500 Ohms
11 Volts
450µA
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
4
1
˝ H x 4˝ W x 1
1
˝ D (Mounts to a 4˝ square by 2
2
4
SMB500 Electrical Box
C1067-00
1
inches. Surface mounted elec-
8
7550 Meridian Circle, Maple Grove, MN 55369-4927
1
˝ deep box.)
8
figure 2. moDule mounting:
NOTE: For UL Listed security installations, the SK-Monitor must be mounted
within the control panel enclosure.
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer), as shown in Figure 2.
1
763-493-6455; 800-328-0103 Fax: 763-493-6475
http://www.silentknight.com
ISOLATED
QUADRANT
I56-3442-000
C1066-00

Advertisement

loading

Summary of Contents for Honeywell Silent Knight SK-Monitor

  • Page 1: Specifications

    inStallation anD maintenance inStructionS 7550 Meridian Circle, Maple Grove, MN 55369-4927 763-493-6455; 800-328-0103 Fax: 763-493-6475 SK-monitor module http://www.silentknight.com SpecificationS Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.0 mA (LED on) Average Operating Current: 375µA (group poll), 350 µA (direct poll), 600 µAmps (communication, IDC shorted) EOL Resistance: 47K Ohms Max.
  • Page 2 figure 3. typical 2-Wire initiating circuit configuration, nfpa Style B or Security SyStemS: NOTE: For UL Listed security installations, the SK-Monitor must be mounted within the control panel enclosure. TO NEXT FROM PANEL OR DEVICE PREVIOUS DEVICE MONITOR MODULE ANY NUMBER OF UL LISTED CONTACT CONNECT MODULES TO LISTED COMPATIBLE CLOSURE DEVICES MAY BE USED.