INSTALLATION AND MAINTENANCE
INSTRUCTIONS
IDP-Monitor Module

Specifications

Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current: 375µA (LED flashing)
EOL Resistance:
Maximum IDC
wiring resistance:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Before Installing
This information is included as a quick reference installa-
tion guide. Refer to the control panel installation manual
for detailed system information. If the modules will be
installed in an existing operational system, inform the
operator and local authority that the system will be tem-
porarily out of service. Disconnect power to the control
panel before installing the modules.
NOTICE: This manual should be left with the owner/
user of this equipment.
General Description
The IDP-Monitor Module is intended for use in intel-
ligent, two-wire systems, where the individual address of
each module is selected using the built-in rotary switches.
It provides either a Class A or Class B fault tolerant initi-
ating device circuit (IDC) for normally open contact fire
alarm and supervisory devices, or either normally open or
normally closed security devices. The module has a panel
controlled LED indicator.
Compatibility Requirements
To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control panel
(list available from Silent Knight).
K200-08-00
15 to 32 VDC
5.0 mA (LED on)
47K Ohms
1,500 Ohms
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
4
1
˝ H x 4˝ W x 1
1
˝ D
2
4
(Mounts to a 4˝ square by
2
1
˝ deep box.)
8
SMB500 Electrical Box
Mounting
The IDP-Monitor mounts directly to 4˝ square electri-
cal boxes (see Figure 2A). The box must have a mini-
mum depth of 2
1
˝. Surface mounted electrical boxes
8
(SMB500) are available from Silent Knight.
Wiring
NOTE: All wiring must conform to applicable local
codes, ordinances, and regulations. This module is in-
tended for power limited wiring only.
1. Install module wiring in accordance with the job draw-
ings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer),
as shown in Figure 2A.
Figure 1. Controls and Indicators:
9
8
7
6
5
LOOP
Figure 2A. Module mounting:
NOTE: For UL Listed security installations, the IDP-Monitor
must be mounted within the control panel enclosure.
C0156-00

0
7 8
9
6
5
4
1
3
2
2
1 0
TENS
6 7 8 9
5
3
4
3
4
2
1
0
ONES
ADDRESS
C0218-01
Figure 2B:
C0157-00
I56-2724-002

Advertisement

loading

Summary of Contents for Honeywell Silent Knight IDP-Monitor

  • Page 1: Specifications

    Mounting The IDP-Monitor mounts directly to 4˝ square electri- cal boxes (see Figure 2A). The box must have a mini- mum depth of 2 ⁄ ˝. Surface mounted electrical boxes (SMB500) are available from Silent Knight. Wiring NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.
  • Page 2 Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B: TO NEXT FROM PANEL OR DEVICE PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE SILENT KNIGHT CONTROL PANELS ONLY TENS 6 7 8 9 SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. ONES TWISTED PAIR ADDRESS...