1.3.3

Mode Switching

Change the internal rotary switch and jumper settings according to the output analog
signal.
Supplementary
• Always set the rotary switch and jumpers to the same mode.
• The calibration is initialized when the output mode is changed with jumpers.
• Set jumpers after removing the module from the base unit.
• Do not directly touch the printed circuit boards inside the module.
• The factory setting is ± 10 V (voltage output) and 0 to 20 mA (current output).
• Note that analog conversion cannot be performed correctly if the jumper and rotary switch
settings are other than those in the above table.
• Keep the extra jumper plugs, which may be needed when changing the output specification.
• Do not turn the trimmer (variable resister) which is pre-adjusted.
6F8C0869
Mode specification rotary switch
Match the tip of the
arrow to a number.
Mode specification jumper
Jumper plug
Indicates ±10V voltage output
mode.
1.3 DA364/DA374
Replace the
jumper plug with a
tweaser.
25
1