Toshiba V Series User Manual page 57

Analog module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

(2) Module status
Module status is a read only register containing the module status and error
information. Use the MREAD command to read this register.
0 15
14
RDY ERR 0
bit
15
14
Supplementary
• When error occurs, turn off the system power and then turn it back on.
• A write count alarm is issued when the number of offset calibration write to EEPROM
exceeds 1 million times.
Do not perform unnecessary write because the reliability of the data will be affected when
write to EEPROM exceeds 1 million times.
6F8C0869
0 11
13
12
10
9
0
0 0
0
0
Error code
00H
Normal
11H
CPU abnormal
12H
Watchdog timer abnormal
13H
Work RAM abnormal
14H
I/O port abnormal
21H
ROM BCC abnormal
31H
Common memory abnormal
41H
EEPROM BCC abnormal
42H
EEPROM write abnormal
43H
EEPROM write count alarm
51H
Analog power abnormal
Name
RDY (Ready)
1: Digital conversion data valid
0: Digital conversion data invalid
(During initialization or when error occurs)
ERR (Error)
1: Error
(Error content depends on error code)
0: No error
0 7
0 3
8
6
5
4
0
0
0
Error code
Content (when ERR=1)
Content
1.4 RT318
2
1
0
Status after
occurrence
Normal
Down
Normal
Down
45
1