1.2.3
Mode Switching
Change the jumper settings according to the input analog signal.
Supplementary
• The calibration is initialized when the input mode is changed with jumpers.
• Set jumpers after removing the module from the base unit.
• Do not directly touch the printed circuit boards inside the module.
• The factory setting is ±10 V voltage input mode.
• Note that analog conversion may not be performed properly (FLT turns on) if the jumpers are
set other than above.
• Keep the extra jumper plugs, which may be needed when changing the input specification.
• Do not turn the trimmer (variable resister) which is pre-adjusted.
6F8C0869
Jumper plug
Jumper setting: Shows
± 10 V voltage input mode.
± 5V bipolar voltage input
± 10V bipolar voltage input
0 to 5 V unipolar voltage input
0 to 10 V unipolar voltage input
1 to 5 V unipolar voltage input
± 20 mA bipolar current input
0 to 20 mA unipolar current input
4 to 20 mA unipolar current input
Shorted
(Jumper plug attached)
Opened
(Jumper plug removed)
1.2 AD368
1
Replace jumper
plug with
tweasers.
11