Hitachi WJ200-007MF Manual page 15

Pursuing the ideal compact inverter
Table of Contents

Advertisement

Code
Function Name
b021
Overload restriction operation mode
b221
Overload restriction operation mode, 2nd motor
b022
Overload restriction level setting
b222
Overload restriction level setting, 2nd motor
b023
Deceleration rate at overload restriction
b223
Overload restriction operation mode, 2nd motor
b024
Overload restriction operation mode 2
b025
Overload restriction level 2 setting
b026
Deceleration rate 2 at overload restriction
b027
OC suppression selection
b028
Current level of active freq. matching restart setting
b029
Deceleration rate of frequency matching restart setting
b030
Start freq. to be used in case of active freq. Matching restart 00 (frequency at the last shutoff) / 01 (maximum frequency) / 02 (set frequency)
b031
Software lock mode selection
b033
Motor cable length parameter
b034
Run / power ON warning time
b035
Rotation direction restriction
b036
Reduced voltage start selection
b037
Function code display restriction
b038
Initial-screen selection
b039
Automatic user parameter setting
b040
Torque limit selection
b041 – b044 Torque limit (1) – (4)
b045
Torque LAD STOP selection
b046
Reverse run protection
b049
Dual Rating Selection
b050
Selection of the nonstop operation
b051
Nonstop operation start voltage setting
b052
OV-LAD Stop level of nonstop operation setting
b053
Deceleration time of nonstop operation setting
b054
Frequency width of quick deceleration setting
b060
Maximum-limit level of window comparators O
b061
Minimum-limit level of window comparators O
b062
Hysteresis width of window comparators O
b063
Maximum-limit level of window comparators OI
b064
Minimum-limit level of window comparators OI
b065
Hysteresis width of window comparator (OI)
b070
Operation level at O disconnection
b071
Operation level at OI disconnection
b075
Ambient temperature
b078
Watt-hour reset
b079
Watt-hour display gain setting
b082
Start frequency adjustment
b083
Carrier frequency setting
b084
Initialization mode (parameters or trip history)
b085
Country for initialization
b086
Frequency scaling conversion factor
b087
STOP key enable
Setting Range
00 (disabled) / 01 (enabled during acceleration and constant-speed operation) /
02 (enabled during constant-speed operation) /
03 (enabled during acceleration and constant-speed operation [speed increase at regeneration])
Set a level between 20% and 200% / 150% for the rated inverter current [A] (CT / VT)
0.1 to 999.9 / 1000. to 3000. [s]
0.1 to 999.9 / 1000. to 3000. [s]
00 (disabled) / 01 (enabled during acceleration and constant-speed operation)/
02 (enabled during constant-speed operation) /
03 (enabled during acceleration and constant-speed operation [speed increase at regeneration])
Set a level between 20% and 200% / 150% for the rated inverter current [A] (CT / VT)
0.1 to 999.9 / 1000. to 3000. [s]
00 (disabled) / 01 (enabled)
Set a level between 20% and 200% / 150% for the rated inverter current [A] (CT / VT)
0.1 to 999.9 / 1000. to 3000. [s]
00 (all parameters except b031 are locked when [SFT] terminal is ON) /
01 (all parameters except b031 and output frequency F001 are locked when [SFT] terminal is ON) /
02 (all parameters except b031 are locked) /
03 (all parameters except b031 and output frequency F001 are locked) /
10 (High level access including b031)
5 to 20
0 to 9999. (0 to 99990 [hr ]) / 1000 to 6553 (100000 to 655350 [hr ])
00 (Enable for both dir) / 01 (Enable for forward only) / 02 (Enable for reverse only)
0 (minimum reduced voltage start time) to 255 (maximum reduced voltage start time)
0 (full display) / 1 (function-specific display) / 2 (user setting) /
3 (data comparison display) / 4 (basic display) / 5 (monitor display)
000 (Func. code that SET key pressed last displayed) /
001 to 060 (d001 to d060) / 201 (F001) /
202 (Screen displayed when the STR key was pressed last)
00 (disabled) / 01 (enabled)
00 (quadrant-specific setting) / 01 (switching by terminal) / 02 (O input)
0 to 200 [%] / no
00 (disabled) / 01 (enabled)
00 (disabled) / 01 (enabled)
00 (CT mode) / 01 (VT mode)
[1-phase 100V class is only with CT]
00 (disabled) / 01 (enabled) /
02 (nonstop operation at momentary power failure [no restoration]) /
03 (nonstop operation at momentary power failure [restoration to be done])
0.0 to 999.9 / 1000. [V]
0.0 to 999.9 / 1000. [V]
0.1 to 999.9 / 1000. to 3600. [s]
0.00 to 10.00 [Hz]
0 to 100 [%]
0 to 100 [%]
0 to 10 [%]
0 to 100 [%]
0 to 100 [%]
0 to 10 [%]
0 to 100 [%] / no
0 to 100 [%] / no
-10 to 50 [
º
C]
00 (OFF) / 01 (ON)
1 to 1000
0.10 to 9.99 [Hz] ( to 200Hz)
2.0 to 15.0 [kHz]
00 (disabled) / 01 (clearing the trip history) / 02 (initializing the data) /
03 (clearing the trip history and initializing the data) /
04 (clearing the trip history and initializing the data and EzSQ program)
00 / 01
0.01 to 99.99
00 (enabled) /
01 (disabled) /
02 (disabled only stop)
[ ○ = Allowed × = Not parmitted]
Setting During
Change During
Default
Operation
Operation
Setting
(allowed or not)
(allowed or not)
×
01
×
01
×
150% of
Rated current
×
×
1.0
×
1.0
×
01
150% of
×
Rated current
×
1.0
×
01
Rated current
×
of inverter
×
0.5
×
00
×
01
10
×
0
×
×
00
×
2
×
04
×
001
×
00
×
00
×
200
×
00
×
01
×
×
00
×
×
00
×
×
220 / 440
×
×
360 / 720
×
×
1.00
×
×
0.00
100
0
0
100
0
0
×
no
×
no
40
00
1
×
0.50
×
2.0
×
×
00
×
×
00
1.00
×
00
 15