Code
Function Name
C001
Terminal [1] function
C002
Terminal [2] function
C003
Terminal [3] function
C004
Terminal [4] function
C005
Terminal [5] function
C006
Terminal [6] function
C007
Terminal [7] function
C011 – C017 Terminal [1] – [7] active state
C021
Terminal [11] function
C022
Terminal [12] function
C026
Alarm relay terminal function
C027
EO signal selection (Pulse / PWM output)
C028
[AM] signal selection
C030
Digital current monitor reference value
C031
Terminal [11] active state
C032
Terminal [12] active state
C036
Alarm relay active state
C038
Output mode of low load detection signal
C039
Low load detection level
C040
Output mode of overload warning
Setting Range
00 (FW: Forward Run) / 01 (RV: Reverse RUN) / 02 (CF1: Multispeed 1setting) /
03 (CF2: Multispeed 2 setting) / 04 (CF3: Multispeed 3 setting) /
05 (CF4: Multispeed 4 setting) / 06 (JG: Jogging) / 07 (DB: external DC braking) /
08 (SET: Set 2nd motor data) / 09 (2CH: 2-stage acceleration/deceleration) /
11 (FRS: free-run stop) / 12 (EXT: external trip) / 13 (USP: unattended startprotection) /
14 (CS: commercial power source enable) / 15 (SFT: software lock) /
16 (AT: analoginput voltage/current select) / 18 (RS: reset) /
19 (PTC (only C005): Thermistor input) / 20 (STA: starting by 3-wire input) /
21 (STP: stopping by 3-wire input) / 22 (F/R: forward/reverse switching by 3-wire input) /
23 (PID: PID disable) / 24 (PIDC: PID reset) / 27 (UP: remote control UP function) /
28 (DWN: remote control DOWN function) / 29 (UDC: remote control data clearing) /
31 (OPE: forcible operation) / 32 (SF1: multispeed bit 1) / 33 (SF2: multispeed bit 2) /
34 (SF3: multispeed bit 3) / 35 (SF4: multispeed bit 4) / 36 (SF5: multispeed bit 5) /
37 (SF6: multispeed bit 6) / 38 (SF7: multispeed bit 7) /
39 (OLR: overload restriction selection) / 40 (TL:torque limit enable) /
41 (TRQ1: torque limit selectionbit 1) / 42 (TRQ2: torque limit selection bit 2) /
44 (BOK: braking confirmation) / 46 (LAC: LAD cancellation) /
47 (PCLR: clearance of position deviation) /
50 (ADD: trigger for frequency addition[A145]) / 51 (F-TM: forcible-terminal operation) /
52 (ATR: permission of torque command input) / 53 (KHC: cumulative power clearance) /
56 (MI1: general-purpose input 1) / 57 (MI2: general-purpose input 2) /
58 (MI3: general-purpose input 3) / 59 (MI4: general-purpose input 4) /
60 (MI5: general-purpose input 5) / 61 (MI6: general-purpose input 6) /
62 (MI7: general-purpose input 7) / 65 (AHD: analog command holding) /
66 (CP1: multistage position settings selection 1) /
67 (CP2: multistage position settings selection 2) /
68 (CP3: multistage position settings selection 3) /
69 (ORL: Zero-return limit function) / 70 (ORG: Zero-return trigger function) /
73 (SPD: speed / position switching) / 77 (GS1: safety input 1) / 78 (GS2: safety input 2) /
81 (485: EzCOM) / 82 (PRG: executing EzSQ program) /
83 (HLD: retain output frequency) / 84 (ROK: permission of run command) /
85 (EB: Rotation direction detection for V/f with ENC) / 86 (DISP: Display limitation) /
255 (no: no assignment)
00 (NO) / 01 (NC)
00 (RUN: running) / 01 (FA1: constant-speed reached) /
02 (FA2: set frequency overreached) / 03 (OL: overload notice advance signal [1]) /
04 (OD: output deviation for PID control) / 05 (AL: alarm signal) /
06 (FA3: set frequency reached) / 07 (OTQ: over-torque) / 09 (UV: undervoltage) /
10 (TRQ: torque limited) / 11 (RNT: operation time over) / 12 (ONT: plug-in time over) /
13 (THM: thermal alarm signal) / 19 (BRK: brake release) / 20 (BER: braking error) /
21 (ZS: 0 Hz detection signal) / 22 (DSE: speed deviation maximum) /
23 (POK: positioning completed) / 24 (FA4: set frequency overreached 2) /
25 (FA5: set frequency reached 2) / 26 (OL2: overload notice advance signal [2]) /
27 (ODC: analog O input disconnection) / 28 (OIDC: analog OI input disconnection) /
31 (FBV: PID feedback comparison) / 32 (NDc:communication line disconnection) /
33 (LOG1: logicaloperation result 1) / 34 (LOG2: logical operation result 2) /
35 (LOG3: logical operation result 3) / 39 (WAC: capacitor life warning) /
40 (WAF: cooling-fan) / 41 (FR: starting contact signal) / 42 (OHF: heat sink overheat warning) /
43 (LOC: low-current indication signal) / 44 (M01:general-purpose output 1) /
45 (M02: general-purpose output 2) / 46 (M03: general-purpose output 3) /
50 (IRDY: inverter ready) / 51 (FWR: forward rotation) / 52 (RVR: reverse rotation) /
53 (MJA: major failur) / 54 (WCO: window comparator O) /
55 (WCOI: window comparator OI) / 58 (FREF) / 59 (REF) / 60 (SETM) / 62 (EDM) /
63 (OPO: Option) / 255 (no: no assignment)
00 (output frequency) / 01 (output current) / 02 (output torque) /
03 (digital output frequency) / 04 (output voltage) / 05 (input power) /
06 (electronic thermal overload) / 07 (LAD frequency) / 08 (digital current monitoring) /
10 (heat sink temperature) / 12 (general-purpose output YA0) /
15 (Pulse train input monitor) / 16 (option)
00 (output frequency) / 01 (output current) / 02 (output torque) / 04 (output voltage) /
05 (input power) / 06 (electronic thermal overload) / 07 (LAD frequency) /
10 (heat sink temperature) / 11 (output torque [signed value]) /
13 (general-purpose output YA1) / 16 (option)
Set a level between 20% and 200% for the rated inverter current [A]
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (NO) / 01 (NC)
00 (output during acceleration/deceleration and constant-speed operation) /
01 (output only during constant-speed operation)
Set range: 0 to 200% of inverter rated current [A]
00 (output during acceleration / deceleration and constant-speed operation) /
01 (output only during constant-speed operation)
[ ○ = Allowed × = Not parmitted]
Setting During
Change During
Default
Operation
Operation
Setting
(allowed or not)
(allowed or not)
×
00 (FW)
×
01 (RV)
×
02 (CF1)
×
03 (CF2)
×
09 (2CH)
×
18 (RS)
×
13 (USP)
×
00
×
01 (FA1)
×
00 (RUN)
×
05 (AL)
×
07
×
07
Rated current
of inverter
×
00
×
00
×
01
×
01
Rated current
of inverter
×
01
 17