7. Normal operation

7.5 Advanced Settings - Technicians Only

NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 7.4 to enter password to access this menu.
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard

2. Switch ON/OFF

3. Clear Energy
4. Reset Password
5. Power Control
6. Calibrate Energy
7. Special Settings
8. STD. Mode Settings
9.Restore Settings
10. HMI Update
11. Internal EPM set
12. External EPM set
13. Restart HMI
14. Fan Test
15. DSP Update
16. Compensation Set
17. I/V Curve

7.5.1 Selecting Standard

This function is used to select the grid's reference standard (see Figure 7.16).
YES=<ENT> NO=<ESC>
Selecting the "User-Def" menu will access to the following submenu (see Figure 7.17),
OV-G-V1: 400V
OV-G-V1-T: 1.0S
Below is the setting range for "User-Def". Using this function, the limits can be changed
manually. (These voltage values are the phase voltage)
.46.
Standard:G99
Figure 7.16
Figure 7.17
7. Normal operation
OV-G-V1: 300---480V
OV-G-V1-T: 0.01---9S
OV-G-V2: 300---490V
OV-G-V2-T: 0.01---1S
UN-G-V1: 173---336V
UN-G-V1-T: 0.01---9S
UN-G-V2: 132---319V
UN-G-V2-T: 0.01---1S
Startup-T: 10-600S
Table 7.2 Setting ranges for User-Def (L-N)
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
NOTE
For different countries, the grid standard needs to be set as different according to
local requirements. If there is any doubt, please consult Canadian Solar service
technicians for details.
7.5.2 Switch ON/OFF
Figure 7.18 Switch ON/OFF
7.5.2.1 Grid ON/OFF
This function is used to start up or stop the power generation of Canadian Solar Three Phase
Inverter.
Figure 7.18 Set Grid ON/OFF
OV-G-F1: 50.2-63Hz
OV-G-F1-T: 0.01---9S
OV-G-F2: 51-63Hz
OV-G-F2-T: 0.01---9S
UN-G-F1: 47-59.5Hz
UN-G-F1-T: 0.01---9S
UN-G-F2: 47-59Hz
UN-G-F2-T: 0.01---9S
Restore-T: 10-600S
Grid ON/OFF
24H Switch
Grid ON
Grid OFF