3. Installation

3.4.1 Grounding

To effectively protect the inverter, two grounding methods must be performed.
Connect the AC grounding cable (Please refer to section 3.4.3)
Connect the external grounding terminal.
To connect the grounding terminal on the heat sink, please follow the steps below:
1) Prepare the grounding cable: recommend to use the outdoor copper-core cable. The
grounding wire should be at least half size of the hot wires.
2) Prepare OT terminals: M10.
Important:
For multiple inverters in parallel , all inverters should be connected to the
same ground point to eliminate the possibility of a voltage potential existing
between inverter grounds.
3) Strip the ground cable insulation to a suitable length(see Figure 3.15).
Figure 3.15 Suitable length
Important:
B (insulation stripping length) is 2mm~3mm longer than A (OT cable
terminal crimping area) .
.18.
B
A
4) Insert the stripped wire into the OT terminal crimping area and use the hydraulic
clamp to crimp the terminal to the wire (see Figure 3.16).
Figure 3.16 Strip wire
Important:
After crimping the terminal to the wire, inspect the connection to ensure the
terminal is solidly crimped to the wire.
5) Remove the screw from the heat sink ground point.
6) Connect the grounding cable to the grounding point on the heat sink, and tighten the
grounding screw, Torque is 5-6Nm(see figure 3.17).
Figure 3.17 Fixed cable
Important:
For improving anti-corrosion performance,
after ground cable installed, apply silicone or paint.
3. Installation
C
D
Grounding Screw
Torque:5-6NM
.19.