3. Installation
Figure 3.4 Inverter handles
WARNING
Due to the weight of the inverter, contusions or bone fractures
could occur when incorrectly lifting and mounting the inverter.
When mounting the inverter, take the weight of the inverter into
consideration. Use a suitable lifting technique when mounting.

3.3 Mounting the Inverter

The inverter can be mounted to the wall or metal array racking. The mounting holes should be
consistent with the size of the bracket or the dimensions shown in Figure 3.5.
Φ11
11
Figure 3.5 Inverter wall mounting
.12.
636
unit:mm

3.3.1 Wall mounting

Refer to figure 3.6 and figure 3.7 Inverter shall be mounted vertically.
The steps to mount the inverter are listed below.
1. Refer to Figure 3.6, drill holes for expansion bolt(M10*90) based on the hole
diameter of bracket using a precision drill keeping the drill perpendicular to the wall.
Max depth is 90mm.
2. Make sure the bracket is horizontal. And the mounting holes (in Figure 3.6) are marked
correctly. Drill the holes into wall at your marks.
3. Use the suitable mounting screws to attach the bracket on the wall.
Figure 3.6 Inverter wall mounting
4. Lift the inverter and hang it on the bracket, and then slide down to make sure they
match perfectly.
Figure 3.7 Install the inverter
5.
Use screws in the packaging to fix the inverter to the mount bracket
Figure 3.8 Fix the inverter
3. Installation
Torque:30-35NM
Mounting Bracket
Mounting screws
.
Torque:2-3NM