Quick Links

1.
Shipping Package
This shipping package contains the following items
1 x PM-3033 module
2.
series
PM-3033
ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-3033 series that
gives you access to real-time electric usage for three-phase power measurement. With its high accuracy
(<0.5%, PF=1 ), the PM-3033 series can be applied to both low voltage primary side and/or medium/high
voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings
from the monitored equipments in real time under operation.
Direct input from "secondary side 1A/5A" type CTs. Dedicated CTs are no longer needed, which lowers the
cost of implementation.
It operates over a wide input voltages range 10 ~ 500 VAC which allows worldwide compatibility. It also
supports Modbus RTU, Modbus TCP or CANopen protocols for easy integration.
2.1. Caution & Warning
electricians and metering specialist. ICP DAS assumes no responsibility if your electrical installer does not follow
the appropriate national and local electrical codes.
ICP DAS assumes no liability for any damage resulting from the use of this product. ICP DAS reserves the right to
change this manual at any time without notice. The information furnished by ICP DAS is believed to be accurate
and reliable. However, no responsibility is assumed by ICP DAS for its use, not for any infringements of patents or
other rights of third parties resulting from its use.
2.2. Product Warranty & Customer Support
ICP DAS warrants all products free from defects in material and workmanship for a period of one year from the
date of shipping. During the warranty period, we will, at our position, either repair or replace any product that
proves to be defective. To report any defect, please contact :+886-3- 597-3366 or service@icpdas.com.
2.2.1. Limitation of Warranty
This warranty does not apply to defects resulting from unauthorized modification, misuse, or use for reason other
than electrical power monitoring. The supplied meter is not a user-serviceable product.
ICP DAS Co., LTD
PM-3033 series Quick Start
1 x Quick Start
(This Document)
introduction
The meter contains hazardous voltages, and should never be disassembled. Failing to follow
this practice will result in serious injury or death. Any work on or near energized meters,
meter sockets, or other metering equipment could induce a danger of electrical shock. It is
strongly recommended that all work should be performed only by qualified industrial
PM-3033 series Quick Start V1.10
Screw Driver x 1
CD x 1
Page 1

Advertisement

loading

Summary of Contents for ICP DAS USA PM-3033 Series

  • Page 1 With its high accuracy (<0.5%, PF=1 ), the PM-3033 series can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation.
  • Page 2: Installation

    Reconfirm the RST (ABC) phase sequence of the power system.  PM-3033 series can be installed as rail mounting mode or embedded, no need to drill a hole or screw to fix it (rail mounting width can up to the length of 35 mm).
  • Page 3 Make sure the arrow direction sign on Primary CT’s follows current flow direction(K→L). Note: it must be in the same direction. Connect the voltage input terminal N C B A. for PM-3033 series, in the three phase order as follows on N C B A.
  • Page 4 Wiring  1P2W-1CT (PM-3033 series)  1P3W-2CT (PM-3033 series)  3P3W-2CT (PM-3033 series) ICP DAS Co., LTD PM-3033 series Quick Start V1.10 Page 4...
  • Page 5  3P4W-3CT (PM-3033 series)  LED Indicator The PM-3033 series has 2 LED to indicate the unit power status, communication, and power data calculation.  RUN: Green, light up after communication ready. LED will flash when the unit is processing communication.
  • Page 6 Modbus Address SW 1 SW 2 SW 3 SW 4 SW 5 SW 6 ( Node ID) ICP DAS Co., LTD PM-3033 series Quick Start V1.10 Page 6...
  • Page 7 125k(Default) bps 19200 (Default) bps 250k bps 38400 bps 500k bps 115200 bps 1M bps PM-3033 series:Select the different wiring mode (Please select the Software setting, if 1P2W-1CT or 1P3W-2CT is used) Models PM-3033/ PM-3033-CPS PM-3033-MTCP Wiring SW 9 SW 10...
  • Page 8: Specifications

    Power Consumption Dimensions (W x L x H) 127 mm x 100 mm x 33 mm Environment Operating Temperature -20 ~ +70 °C Storage Temperature -25 ~ +80 °C ICP DAS Co., LTD PM-3033 series Quick Start V1.10 Page 8...

This manual is also suitable for:

Pm-3033Pm-3033-mtcp