Temperature
Specifications
Storage
–40°C to 65°C (–40°F to 149°F)
Continuous
10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
operation (for
altitude less than
950 m or 3117 ft)
Maximum
20°C/h (68°F/h)
temperature
gradient
(operating and
storage)
Relative
Specifications
humidity
Storage
5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere must be non-condensing at all times.
Operating
10% to 80% Relative Humidity with 29°C (84.2°F) maximum dew point.
Maximum
Specifications
vibration
Operating
0.26 G
Storage
1.88 G
Maximum
Specifications
shock
Operating
Six consecutively executed shock pulses in the positive and negative x, y, and z axes of 31G for up to 2.6 ms.
Storage
Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Maximum
Specifications
altitude
Operating
30482000 m (10,0006560 ft).
Storage
12,000 m (39,370 ft).
Operating
Specifications
temperature
de-rating
Up to 35 °C (95
Maximum temperature is reduced by 1°C/300 m (33.8°F/984.25 ft) above 950 m (3,117 ft)
°F)
The following section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution are beyond the specified limits and cause equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Particulate
Specifications
contamination
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
at 5 Hz to 350 Hz (operation orientation).
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
rms
NOTE:
Applies to data center environments only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in environments such as an office or factory
floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
Technical specifications
23