Selecting the control cables

Shielding

Only use shielded control cables.
Use a double-shielded twisted pair cable for analog signals. This type of cable is
recommended for the pulse encoder signals also. Employ one individually shielded pair for
each signal. Do not use common return for different analog signals.
A double-shielded cable (figure a below) is the best alternative for low-voltage digital signals
but single-shielded (b) twisted pair cable is also acceptable.
a

Signals in separate cables

Run analog and digital signals in separate, shielded cables. Do not mix 24 V DC and
115/230 V AC signals in the same cable.

Signals that can be run in the same cable

If their voltage does not exceed 48 V, relay-controlled signals can be run in the same cables
as digital input signals. The relay-controlled signals should be run as twisted pairs.

Relay cable type

The cable type with braided metallic screen (for example ÖLFLEX by LAPPKABEL, Germany)
has been tested and approved by ABB.

Control panel to drive connection

Use EIA-485 with male RJ-45 connector, cable type Cat 5e or better. The maximum permitted
length of the cable is 100 m (328 ft).
Electrical planning guidelines 27