CONVERSION TO HIGH ELEVATION
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS
FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
Natural Gas Conversion Kit 730-920 Contains:
Qty. Part # Description
1 904-240 Burner Orifice #37 (NG)
1 918-034 Decal "Converted to 31,000 Btu"
1 918-033 Instruction Sheet
Propane Conversion Kit 730-922 Contains:
Qty. Part # Description
1 904-390 Burner Orifice #52 (LPG)
1 918-034 Decal "Converted to 29,000 Btu"
1 918-033 Instruction Sheet
1) Shut off the gas supply.
2) Open the front door. Carefully remove the logs
and media.
3) Remove burner. See diagram below.
4) Remove burner orifice with a 1/2" wrench and
discard.
Note: Use a magnetic type screwdriver if
possible.
26 |
Regency
U39-11 ULTIMATE™ Freestanding Gas Stove
®
Burner Orifice
5. Reinstall new burner orifice (NG stamped
#37 or LP stamped #52) and tighten.
6. Reverse steps 3. and 2.
7. Adjust Vent restrictor setting: To set the
Vent restriction as indicated in the diagram,
simply loosen the screws and push the vent
restrictor plate to the correct position. Tighten
the screws.
Unit Btu/h
Restrictor Opening
U39
31,000
A 1-3/4" (44mm)
29,000
B 1-1/4" (32mm)
Vent Restrictor set-
Vent Restrictor set-
ting at High Btu/h
ting at Low Btu/h
8. Attach the label
"This unit has been
converted to..." on top of the Serial # decal
over the higher Btu information.
9. Check for gas leaks.
10. Check inlet and outlet pressures.
11. Check operation of flame control. Check for
proper flame appearance and glow on logs.

GAS PIPE PRESSURE TESTING

The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counter clockwise with a 1/8" wide flat
screwdriver.
3. Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4. Light the pilot and turn the valve to "ON" position.
Read manometer.
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ultimate u39U39-lp11

Table of Contents