Small form-factor pluggable intermediate reach

Advertisement

Per GR-1089-CORE Section 9, this product does not have an
internal DC connection between battery return and frame
ground. This product can be installed in a DC-I (isolated) or
DC-C (common) installation. For installations where other
cards or the host system have internal connections between
battery return and frame ground, the system would be
intended for deployment only in a DC-C installation.
The ADTRAN system chassis frame ground terminal must be
connected to an earth ground to ensure that the metal
enclosure of this product is properly grounded via the
backplane connector.
NOTE
The OC-3 port(s) are optical and therefore are not classified as any
type of port as defined in Appendix B of GR-1089-CORE Issue 4.
This product is NRTL Listed to the applicable UL standards. This
product meets or exceeds all the applicable requirements of
NEBS, Telcordia GR-63-CORE, and GR-1089-CORE. This product
is intended for deployment in Central Office type facilities, EEEs,
EECs, and locations where the NEC applies (for example,
Customer Premises). Install this equipment in an ADTRAN
product located in a restricted access location.
This device complies with Part 15 of the FCC rules. Operation is
subject to the following two conditions:
1. This device may not cause harmful interference
2. This device must accept any interference received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by ADTRAN
could void the user's authority to operate this equipment.
This product is designed to meet the following environmental
classes:
ETSI EN 300 019-1-1 Classification of environmental conditions;
Storage, Class 1.2
ETSI EN 300 019-1-2 Classification of environmental conditions,
Transportation, Class 2.3
ETSI EN 300 019-1-3 Classification of environmental conditions,
Stationary use at weather-protected locations, Class 3.3
The OC3 IR SFP 1184543PG2 is designed to be deployed in GR-
3108-CORE environmental class 2 as defined in GR-3108-CORE.
The equipment is designed to function without degradation
during exposure to all test severities per Class 3.3.
For more information, refer to the Installation and Maintenance Guide for the host module,
available online at www.adtran.com.
Warranty:
ADTRAN will replace or repair this product within the warranty period if it does not
meet its published specifications or fails while in service. Warranty information can
be found online at www.adtran.com/warranty.
©2012 ADTRAN, Inc. All Rights Reserved.
From within the U.S.
From outside the U.S. +1 256.963.8716
PRICING AND AVAILABILITY 1.800.827.0807
C A U T I O N !
*61184543PG2-22A*
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY
HANDLING PRECAUTIONS REQUIRED
ADTRAN CUSTOMER CARE:
1.800.726.8663

Advertisement

loading
Need help?

Need help?

Do you have a question about the OC-3 and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

1184543pg2