  Troubleshooting the Meter using SetApp
Check the Energy value in the Meters section of the Status page, as shown in the figure
below:
RS485-1
Modbus ID #2
Power
7.60 kW
If the Energy [in MWh] value displays a steady value even though the the site is
consuming power, check the following:
There are no loose connections at the inverter connectors and at the meter,
specifically the AC wiring on the meter's AC wiring connector.
Check for water damage or sealing problems:
Inspect the entire conduit run for possible points of water penetration, and fix
leaks.
Ensure that proper outdoor rated components are used.
Meters
Export Meter
Status
Comm. Error
Energy
8.42 MWh
Inline Energy Meter with SolarEdge Energy Net Communications