•
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS910 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests
61000-4-2
61000-4-3
61000-4-4
61000-4-5
61000-4-6
61000-4-8
61000-4-11
61000-4-12
RUGGEDCOM RS910
Installation Manual, 04/2021, C79000-G8976-1029-12
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
Test
IEC
ESD
IEC
Radiated RFI
IEC
Burst (Fast Transient)
IEC
Surge
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
Damped Oscillatory
6.2 EMC and Environmental Type Tests
Description
Enclosure
Contact
Enclosure Air
Enclosure
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Enclosure
Ports
AC Power
Ports
Signal Ports
Certification
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
± 4 kV Line-to-Ground
± 2 kV
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m Continuous
1000 A/m for 1 s
100% for 5 Periods
100% for 50 Periods
2.5 kV Common
Mode @ 1 MHz
Severity
Levels
4
4
x
4
4
4
4
3
4
3
3
3
3
3
39