Table 3-2: Pressure Configuration via Class 2 Master
Steps
Set blocks to Out of Service
Select Measurement Type
Select Units
Enter Scaling
Set blocks to Auto
3.6
Host integration
Control host (Class 1)
The Rosemount 2051 device utilizes condensed status as recommended by
the Profile 3.02 specification and NE 107. See manual for condensed status
bit assignment information.
The appropriate GSD file must be loaded on the control host - Rosemount
2051 specific (rmt3333.gsd) or Profile 3.02 Generic (pa139700.gsd). These
files can be found on
Configuration host (class 2)
The appropriate DD or DTM file must be installed in the configuration host.
These files can be found at Emerson.com.
Quick Start Guide
Actions
Put Transducer Block into Out of Service
mode
Put Analog Input Block into Out of Service
mode
Set Primary Value type to Pressure
Set Engineering Units
Primary and secondary units must match
Configure engineering units under analog
output block
Set Scale In in Transducer Block to 0–100
Set Scale Out in Transducer Block to 0–100
Set PV Scale in Analog Input Block to 0–100
Set Out Scale in Analog Input Block to 0–100
Set Linearization in Analog Input Block to No
Linearization
Put Transducer Block into Auto mode
Put Analog Input Block into Auto mode