Safe Circuit Operation Timing; Start Method; Stop Method - Toshiba TSL3000E Series Interface Manual

Robot controller
Hide thumbs Also See for TSL3000E Series:
Table of Contents

Advertisement

4.5

SAFE Circuit Operation Timing

close
EMG-IN1,2~
EMG-OUT1,2
close
SAD-IN1,2~
SAD-OUT1,2
RST-1,2
open
none
Alarm
Servo power circuit
open
4.5.1

Start Method

While all emergency stop switches are canceled, the safety relay module in the
controller is reset by pressing the switch between RST-1 and RST-2. Set the input
width of RST-1 and RST-2 signals to 150 ms (min.) or more. When the safety relay
module is reset, the alarm and servo power circuit enter close status and AC power
is connected to the servo power unit.
Then, voltage charge is started and power is supplied to the motor by inputting the
servo ON command signal.
4.5.2

Stop Method

The stop method varies depending on the status of the master mode switch on the
control front panel.
In TEACH mode, when any of the emergency stop switch, enable switch on the
teach pendant and safety input switch is open, slowdown and stop are started, the
brake signal is then input, and the power to the motor is turned off. In EXT mode,
the enable switch on the teach pendant is disabled, and the robot does not stop
even if the enable switch on the teach pendant is gripped.
When a delay time of 500 ms elapses after any of the emergency stop switch,
enable switch on the teach pendant and safety input switch is open, the servo power
Emergency stop
150msec
– 43 –
INTERFACE MANUAL
500msec
500msec
STE 85457